The Destiny-4100 is compatible with the ADEMCO 4140-BLK removable terminal strips. If

necessary, these connectors allow for quick replacement of the control board.

Wiring Notes

Grounding: Ground the panel to the "com" on far left terminal block as shown in Wiring Diagram on
previous page.
UL recommends attaching the system ground to a cold water pipe, 16ga. at 15 feet.
Although cold water pipes have been the standard for earth ground, it is very common in
modern construction that a cold water pipe does not provide an adequate ground due to
the extensive use of PVC and other styles of "plastic" tubing. The best method for
grounding the panel is to locate the panel in an area with easy access to the power
company's earth ground.
Telephone Operation: In the event of telephone operational problems, disconnect the control panel by removing
the plug from the RJ31X (CA38A in Canada) wall jack. We recommend that you
demonstrate disconnecting the phones on installation of the system. Do not disconnect
the phone connection inside the control panel. Doing so will result in loss of your phone
lines. If the regular phone works correctly after the control panel has been disconnected
from the phone lines, the control panel has a problem and should be returned for repair.
If upon disconnection of the control panel, there is still a problem on the line, notify the
telephone company and request prompt repair service. The user may not under any
circumstance (in or out of warranty) attempt any service or repairs to the system. It must
be returned to the factory for all repairs.
Communicator: Connection of the fire alarm signal to a fire alarm headquarters or a central station shall
be permitted only with the permission of the local authority having jurisdiction. The
burglary alarm signal shall not be connected to a police emergency number.
Codes: This equipment should be installed in accordance with National Fire Protection
Association's Standard 74 (National Fire Protection Association, Battery March Park,
Quincy, MA 02269). Printed information describing proper installation, operation,
testing, maintenance, evacuation planning and repair service is to be provided with this
equipment.
Compliance: This device complies with part 15 of FCC rules. Operation is subject to the following two
conditions: (1) It may not cause harmful interference. (2) It must accept any interference
that may cause undesired operation.
Complies with Part 68 of the FCC rules for direct telephone interconnect.
FCC Registration Number: 107USA-74224-AL-T
Ringer Equivalence: 0.8
Use USOC RJ-31X telephone connection jack. Complies with ANSI/UL 1023 Household
Burglary Alarm System Units and ANSI/UL 985 Household Fire Warning System Units.
Connections: Use UL Listed Cable for all connections.
Testing: Weekly testing is required to ensure proper operation of this system
Servicing: To prevent the risk of shock, disconnect telephone line at telephone company supply jack
before servicing this unit.
Battery: Battery normally need not be replaced for at least 3 years. Use a 12 volt 7Ah battery
(minimum). For all UL installations use two 12 volt 7Ah batteries wired in parallel.