21
Zone 1 Zone 2
Input Control Board Loop 1 Input Control Board Loop 2
Option Location Default New Value Option Location Default New Value
Zone Type 0647 255 Zone Type 0663 255
Option 1 0643 080 Option 1 0659 080
Option 2 0644 000 Option 2 0660 000
Supervision 1106 000 Supervision 1110 000
Word 1 Word 3 Word 1 Word 3
Word 2 Word 4 Word 2 Word 4
Zone 3 Zone 4
Input Control Board Loop 3 Input Control Board Loop 4
Option Location Default New Value Option Location Default New Value
Zone Type 0679 255 Zone Type 0695 255
Option 1 0675 080 Option 1 0691 080
Option 2 0676 000 Option 2 0692 000
Supervision 1114 000 Supervision 1118 000
Word 1 Word 3 Word 1 Word 3
Word 2 Word 4 Word 2 Word 4
Zone 5 Zone 6
Input Control Board Loop 5 Input Control Board Loop 6
Option Location Default New Value Option Location Default New Value
Zone Type 0711 255 Zone Type 0727 255
Option 1 0707 080 Option 1 0723 080
Option 2 0708 000 Option 2 0724 000
Supervision 1122 000 Supervision 1126 000
Word 1 Word 3 Word 1 Word 3
Word 2 Word 4 Word 2 Word 4
Zone 7 Zone 8
Input Control Board Loop 7 Input Control Board Loop 8
Option Location Default New Value Option Location Default New Value
Zone Type 0743 255 Zone Type 0759 255
Option 1 0739 080 Option 1 0755 080
Option 2 0740 000 Option 2 0756 000
Supervision 1130 000 Supervision 1134 000
Word 1 Word 3 Word 1 Word 3
Word 2 Word 4 Word 2 Word 4

Zones 1 - 8: System Controller

At default, all 8 system inputs are disabled. To enable a hardware input, enter a zone type in the zone type
location.
Example: To enable Zone 1 (Input 1) and assign it as an Exterior Instant, enter 0647,000
Generally, this is all of the programming necessary to activate a zone. There are 4 spaces in each zone record to
note a zone description. At the end of the zone programming section are detailed instructions for entering zone
descriptions and a complete listing of the system vocabulary.
Other options:
Each input is defaulted to use a single End-Of-Line Resistor(EOLR). For certain installations, it may be necessary to
use full 2-resistor supervision or for ease of installation, no EOLR. To adjust the supervision setting, enter the
appropriate value in the supervision location.
Options Value
2 end-of-line resistor supervision .................................................................................................... 064
No end of line resistor (Not permitted in a UL installation) ............................................................. 128
Default (1 end-of-line resistor) ....................................................................................................... 000