Specifications

Electrical: Voltage Input: 16.5 VAC 40 VA from supplied transformer
External Speaker: 10 Watt minimum, 8 horn type - Ademco 713 or equivalent. Total
speaker load must be between 4 and 16.
Internal Speaker: Speaker supplied in all compatible keypads. For stand-alone operation
10 Watt minimum, 8 - Ademco 747 or equivalent. Total speaker load must be
between 4 and 16. For UL installations use a UL residential fire listed speaker.
Auxiliary Power Output: 13.5VDC, 1.85 AMP max - Not to be used in a UL installation
Switched Fire Output: 13.5VDC, 1.85 AMP max
Two Wire Smoke Detectors: Up to 12 per system
Note: Switched Fire Output and Two Wire Smoke Detectors are not to exceed
10 mA in a UL installation
Back-up Battery: 12VDC, 7AH gel cell. YUASA NP7-12 or equivalent.
For UL installations use 2 - batteries with SA5140-1 cable assembly
CAUTION: Total current draw of Auxiliary + 4 wire bus power is not to exceed 2 Amps.
Test installation for 1 minute in alarm to ensure sufficient power.
Dimensions: 15.1" L x 13.05" W x 3.5" D w/ door.
Nonvolatile Memory: Maintains programming options with no power to the control.
Communicator: Supports: 3/1, 4/1/1, 4/2 extended, Ademco Contact ID
45 report codes
DTMF and pulse dialing
DPDT line seizure
Two telephone numbers and two account codes, dial both numbers
Split reporting of selected codes
Alternate number dialing if primary number fails
Programmable number of dialing attempts
Programmable to enable or disable the communicator
Two-Way Voice: Microphone inputs: 3 separate, individually controlled channels.
Microphone: 5V shielded 2 conductor omnidirectional electret condenser microphone.
Frequency response 50-10K. -64db sensitivity, TWM-25K or equivalent.
System Zones: 16 - programmable fully supervised wireless alarm points
8 - programmable fully supervised hardwire inputs on the control panel
1 - 2-wire smoke loop
1 - keypad alert
1 - local phone activation
1 - remote phone / phone line monitor activation
1 - AC loss / control low battery / communicator
Auxiliary Outputs: 1 - Form C 10A 24V system relay
4 - Pull to ground, 12 volt, 100mA outputs, not to exceed 500mA total.
Not to be used in a UL installation