32
4— Periods WAKE, DAY,EVE, and SLEEP are available.
Defaultis 4.
Option 26 — Minimum Cooling Setpoint
This selection allows the installer to configu re the minimum cooling setpoint that
the user is allowedto set. The range is based on the value of the adjustable
deadband Option 11, such thatthe minimum of the range is 50_Fplusthe
adjustabledeadband and the maximumis 90_F.
Defaultis 52_F (based on the adjustabledeadband default= 2).
Option27 — Maximum Heating Setpoint
This selection allows the installer to configure the maximum heating setpoint.
The range isbased on the adjustable deadbandvalue Option 11, such thatthe
minimumof the range is 50_F and the maximum is 90_F minus thedeadband.
Defaultis 88_F (based on the adjustabledeadband default= 2).
Option28 — UV Light Reminder
This selection allows the installer to select the nu mber of months after which the
UV Light iconwill be displayed to indicate to the homeownerthat it is time to
call the dealer to have the UV Lights replaced. Selection s available are OF (off),
6,12, 18, 24, 30, 36, 42, 48.
OF(off) — The UV Light reminder is turnedoff and will never be displayed.
6--48— The number of months after which the UV Light reminder will be
displayed,“CHECK UV LIGHT”.
Default is OF (off).
Option 29 — Humidifier Pad Reminder
This selectsthe number of months after which the Humidifier Pad Reminder
iconwill be displayed.This is not based on run time.