30GN040-420
Controls, Operation, and Troubleshooting
ACCESSORY UNLOADER INSTALLATION
Keypad and Display Module
MAJOR SYSTEM COMPONENTS
SAFETY CONSIDERATIONS
GENERAL
Table 1 Ð Unit Sizes and Modular Combinations
TB Ð Terminal Block
Fig. 1 Ð 30GN Control Panel 040-110Unit Shown
LEGEND CCN Ð Carrier Comfort Network
Keypad and Display Module Also Called HSIO
OPERATION DATA
Fig. 3 Ð Compressor Ground Fault Module
Compressor Protection Control Module CPCS
Table 3 Ð Thermistor and Transducer Locations
Table 4A Ð Capacity Control Steps
Table 4A Ð Capacity Control Steps, 040-070cont
Table 4A Ð Capacity Control Steps, 040-070cont
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
UNIT
LOADING SEQUENCE A
LOADING SEQUENCE A
A1*,B1
LOADING SEQUENCE A
A1,kB1
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
Keypad and Display Module Also Called HSIO
Head Pressure Control
Pumpout
Fig. 4 Ð Keypad and Display Module
Table 5 Ð Condenser Fan Sequence
Table 6 Ð Keypad and Display Module Usage
Table 7 Ð Functions and Subfunctions
Table 8 Ð Accessing Functions and Subfunctions
Table 9 Ð Keypad Directory STATUS
SUBFUNCTION
6 TEMPERATURE
Table 9 Ð Keypad Directory cont STATUS cont
KEYPAD ENTRY
KEYPAD ENTRY
Table 9 Ð Keypad Directory cont STATUS cont
SUBFUNCTION
DISPLAY
Table 9 Ð Keypad Directory cont STATUS cont
TEST
Table 9 Ð Keypad Directory cont TEST cont
SCHEDULE
SERVICE
Table 9 Ð Keypad Directory cont SCHEDULE cont
Table 9 Ð Keypad Directory cont SERVICE cont
SUBFUNCTION
3 ALARM/ALERT
Table 9 Ð Keypad Directory cont HISTORY
KEYPAD ENTRY
Table 9 Ð Keypad Directory cont SET POINT
Example 1 Ð Reading Alarm Codes
Example 2 Ð Reading Current Operating Modes
Table 10 Ð Operational and Mode Display Codes
Chilled Fluid Set Point
Example 3 Ð Using Test Function
Reset Set Points
Pulldown Set Point
Example 4 Ð Reading and Changing
Example 5A Ð External Reset
Table 11 Ð Reset Amounts
Chilled Fluid Set Point
Fig. 5 Ð Cooling Return Fluid Reset
Externally Powered Reset
Example 5C Ð Using Return Fluid Temperature Reset
Example 5B Ð 4 to 20 mA and Internally or
Ð Switch
Fig. 6 Ð Cooling External Temperature Reset
Ð Power
COMM Ð Communications Bus
Table 12 Ð Service Functions
Fig. 8 Ð 4-20mA Cooling Temperature Reset
Example 6 Ð Changing Reset Type
Externally powered
Example 8 Ð Setting Time of Day and Day of Week
To Disable Demand Limit
Example 7B Ð Using Demand Limit 4-20mA
First Log On As Shown in Table
Fig. 9 Ð 4-20mA Demand Limiting
To change a conguration enter the new conguration
Table 14 Ð Adjustable Field Congurations
Table 13 Ð Factory Conguration Keystrokes
and press while on the correct conguration
Example 9 Ð Using the Schedule Function
Example 9 Ð Using the Schedule Function cont
Fig. 10 Ð Sample Time Schedule
TROUBLESHOOTING
Example 10 Ð Holiday Schedule Function
Cooling load satised
Table 16 Ð Alarm and Alert Codes
Table 16 Ð Alarm and Alert Codes cont
Fig. 11A Ð 24-VSafety Circuit Wiring
Code 30 Reset input failure 4 to 20 mA alert
Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vac supplying the PSIO, DSIO-LV,or 4 IN/4 OUT the 12.5-vactrans- former supplying the DSIO-EXVmodule, or the 24-vactrans- former supplying PS1 for the transformers. These transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are not grounded
Code 42 Cooler freeze protection alarm
Electronic Expansion Valve EXV
Fig. 12 Ð Electronic Expansion Valve EXV
Fig. 13 Ð EXV Cable Connections to EXV Driver
Module, DSIO EXV
6.Check operation of EXV
TEMPERATURE
TEMPERATURE
1.Disconnect transducer from the system
ALL UNITS AND FLUID-SIDETEMPERATURE
FLUID-SIDETEMPERATURE THERMISTOR T2
COMPRESSOR SUCTION GAS TEMPERATURE
Fig. 15 Ð Thermistor Locations
TRANSDUCER REPLACEMENT
Control Modules
Fig. 20 Ð Processor Module PSIO
ACCESSORY UNLOADER INSTALLATION
Fig. 19 Ð Sensor Bus Wiring Communications
Fig. 21 Ð Low-VoltageRelay Module DSIO
Installation
Fig. 22 Ð 4 In/4 Out Module SIO
Table 19 Ð Troubleshooting
Table 20 Ð Standard and Accessory Unloaders
Press
3.Wire in the solenoid valves
pad display reads OUTPUTS. Press until display
The keypad LCD will display
See Table
Fig. 30 Ð Remote Reset from 4-20mA Signal
Switch Inputs
Fig. 26 − Demand Limit Ð 4-20mA Signal
Externally Powered
REPLACING DEFECTIVE PROCESSOR MODULE
Installation
Fig. 34 Ð Remote Alarm
Fig. 35 Ð Interlocks
Page
Copyright 1995 Carrier Corporation