Carrier 30GN040-420 operating instructions Ð Alarm and Alert Codes

Models: 30GN040-420

1 72
Download 72 pages 43.68 Kb
Page 49
Image 49

Table 16 Ð Alarm and Alert Codes

 

ALARM

 

ACTION TAKEN

CIRCUIT

RESET

 

DISPLAY

OR

DESCRIPTION

BY CONTROL

PUMPDOWN

METHOD

PROBABLE CAUSE

 

ALERT

 

 

 

 

 

0

Ð

No Alarms or Alerts Exist

Ð

Ð

Ð

Ð

1

 

Compressor A1 failure

Circuit A shut down

No

Manual

High-pressure switch trip, or wiring

 

 

 

 

 

 

error.

2, 3, 4

Alert

Compressor A2, A3, A4 failure

Compressor shut down

Yes

Manual

CPCS Ground Fault Protection

5

 

Compressor B1 failure

Circuit B shut down

No

Manual

 

6, 7, 8

 

Compressor B2, B3, B4 failure

Compressor shut down

Yes

Manual

 

 

 

 

 

 

 

 

9

Alarm

Leaving ¯uid thermistor failure

Unit shut down

Yes

Auto.

 

10

Entering ¯uid thermistor failure

Unit shut down

Yes

Auto.

 

 

Thermistor or transducer failure

19

 

Compressor A1 sensor failure

Circuit A shut down

Yes

Auto.

 

 

or wiring error.

20

Alert

Compressor B1 sensor failure

Circuit B shut down

Yes

Auto.

 

21

 

Reset thermistor failure

Normal set point used

No

Auto.

 

 

 

 

 

 

 

 

22

 

Discharge pressure transducer failure, circuit A

Circuit A shut down

Yes

Auto.

 

23

 

Discharge pressure transducer failure, circuit B

Circuit B shut down

Yes

Auto.

 

24

Alert

Suction pressure transducer failure, circuit A

Circuit A shut down

No

Auto.

Transducer failure or wiring error.

25

Suction pressure transducer failure, circuit B

Circuit B shut down

No

Auto.

 

 

26

 

Oil pressure transducer failure, circuit A

Circuit A shut down

No

Auto.

 

27

 

Oil pressure transducer failure, circuit B

Circuit B shut down

No

Auto.

 

 

 

 

 

 

 

 

28

Alarm

Transducer supply voltage low

Unit shut down

No

Auto.

Unit voltage low or PS1 faulty.

29

LOCAL/ENABLE-STOP-CCN

Unit shut down

No

Manual

Switch failure or wiring error.

 

 

 

 

 

 

 

 

30

Alert

4-20 mA reset input failure

Normal set point used

No

Auto.

 

31

4-20 mA demand limit failure

Demand limit ignored

No

Auto.

 

 

 

32

 

Loss of communication with DSIO-LV

Unit shut down

No

Auto.

Wiring error or faulty module

 

 

Alarm

 

 

 

 

or improper address code.

33

Loss of communication with DSIO-EXV

Unit shut down

No

Auto.

 

 

 

34

 

Loss of communication with 4 In/4 Out module

Unit shut down

Yes

Auto.

 

 

 

 

 

 

 

 

35

Ð

Not used

Ð

Ð

Ð

Ð

 

 

 

 

 

 

 

36

 

Low refrigerant pressure circuit A

Circuit A shut down

No

*

Low refrigerant charge, plugged ®lter

 

Alert

 

 

 

 

drier, faulty expansion valve.

37

Low refrigerant pressure circuit B

Circuit B shut down

No

*

Low refrigerant charge, plugged ®lter

 

 

 

 

 

 

 

drier, faulty expansion valve.

 

 

 

 

 

 

 

38

 

Failure to pump out circuit A

Circuit A shut down

No

Manual

Faulty expansion valve, transducer,

 

Alert

 

 

 

 

or thermistor.

39

Failure to pump out circuit B

Circuit B shut down

No

Manual

Faulty expansion valve, transducer,

 

 

 

 

 

 

 

or thermistor.

 

 

 

 

 

 

 

40

 

Low oil pressure circuit A

Circuit A shut down

No

Manual

Low oil level, circuit breaker trip,

 

 

 

 

 

 

faulty expansion valve, crankcase

 

Alert

 

 

 

 

heater, or pressure transducer.

41

Low oil pressure circuit B

Circuit B shut down

No

Manual

Low oil level, circuit breaker trip,

 

 

 

 

 

 

 

faulty expansion valve, crankcase

 

 

 

 

 

 

heater, or pressure transducer.

42

 

Cooler freeze protection

Unit shut down

No

*

Low ¯uid ¯ow or faulty thermistor.

43

Alarm

Low cooler ¯uid ¯ow

Unit shut down

No

Manual

Chilled ¯uid pump failure

44

 

 

 

 

 

or faulty thermistor.

 

 

 

 

 

 

Low suction temperature circuit A

Circuit A shut down

No

Manual

Faulty expansion valve or thermistor.

 

Alert

 

after 10 minutes

 

 

 

45

Low suction temperature circuit B

Circuit B shut down

No

Manual

Faulty expansion valve or thermistor.

 

 

 

 

after 10 minutes

 

 

 

46

 

High suction superheat circuit A

Circuit A shut down

Yes

Manual

Low charge, faulty expansion valve or

 

Alert

 

 

 

 

thermistor, or plugged ®lter drier.

47

High suction superheat circuit B

Circuit B shut down

Yes

Manual

Low charge, faulty expansion valve or

 

 

 

 

 

 

 

thermistor, or plugged ®lter drier.

 

 

 

 

 

 

 

48

Alert

Low suction superheat circuit A

Circuit A shut down

Yes

Manual

Faulty EXV or thermistor.

49

Low suction superheat circuit B

Circuit B shut down

Yes

Manual

Faulty EXV or thermistor.

 

 

 

 

 

 

 

 

50

 

Illegal con®guration

Unit cannot start

Ð

Manual

Con®guration error.

51

Alarm

Initial con®guration required

Unit cannot start

Ð

Manual

Con®guration omitted.

52

 

Emergency stop by CCN command

Unit shut down

Yes

CCN

Network command.

 

 

 

 

 

 

 

53

 

Cooler pump interlock failure

Unit shut down

No

Manual

Failure of cooler pump or controls

54

Alarm

Cooler pump interlock failure

Unit shut down

No

Manual

Failure of cooler pump or controls

55

 

Cooler pump interlock failure

Cooler pump shut down

Ð

Manual

Failure of cooler pump relay or interlock

56

Alert

WSM communication failure

WSM forces removed

Ð

Auto.

Wiring fault or module failure

 

 

 

 

 

 

 

57

 

Calibration required for discharge pressure

Circuit cannot start

Ð

Auto.

 

 

 

transducer, circuit A

 

 

 

 

58

 

Calibration required for discharge pressure

Circuit cannot start

Ð

Auto.

 

 

 

transducer, circuit B

 

 

 

 

59

 

Calibration required for suction pressure

Circuit cannot start

Ð

Auto.

 

 

Alert

transducer, circuit A

 

 

 

Transducer not calibrated

60

Calibration required for suction pressure

Circuit cannot start

Ð

Auto.

 

 

 

 

transducer, circuit B

 

 

 

 

61

 

Calibration required for oil pressure

Circuit cannot start

Ð

Auto.

 

 

 

transducer, circuit A

 

 

 

 

62

 

Calibration required for oil pressure

Circuit cannot start

Ð

Auto.

 

 

 

transducer, circuit B

 

 

 

 

49

Page 49
Image 49
Carrier 30GN040-420 operating instructions Ð Alarm and Alert Codes