Fig. 19 Ð Sensor Bus Wiring
(Communications)
PROCESSOR MODULE (PSIO) (Fig. 20)
Inputs Ð Each input channel has 3 terminals; only 2 of the terminals are used. Application of machine determines which terminals are used. Always refer to individual unit wiring for terminal numbers.
Outputs Ð Output is 24 vdc. There are 3 terminals, only 2 of which are used, depending on application. Refer to unit wiring diagram.
NOTE: Address switches (see Fig. 20) must be set at 01 (dif- ferent when CCN connected).
LOW VOLTAGE RELAY MODULE
Inputs Ð Inputs on strip J3 are discrete inputs (ON/OFF). When
Outputs Ð Terminal strips J4 and J5 are internal relays whose coils are
4 IN/4 OUT MODULE (SIO) (Fig. 22) Ð 4 In/4 Out mod- ule allows the following features to be utilized:
1.Temperature Reset by outdoor air or space temperature. A remote thermistor (Part No. 30GB660002) is also re- quired.
NOTE: This accessory is not required for return water temperature reset.
2.Temperature Reset by remote 4 to 20 mA signal.
3.Demand Limit by remote
4.Demand Limit by remote 4 to 20 mA signal
5.Dual Set Point by remote switch.
The options module is standard. Remember to recon®g- ure the chiller for each feature selected (see Table 14). For temperature reset, demand limit, and dual set point, desired set points must be entered through keypad and display mod- ule (see Set Point Function section on page 38).
See Table 19 for overall troubleshooting information.
ACCESSORY UNLOADER INSTALLATION
Some of the 30G Flotronic™ II units come standard with unloader(s), and many permit additional unloader(s) to be added if desired. See Table 20.
IMPORTANT: The following combinations ARE NOT permitted (combinations are per circuit):
1.Two unloaders and hot gas bypass
2.Four compressors and 2 unloaders.
3.Four compressors, 1 unloader, and hot gas bypass.
PWR Ð Power
Fig. 20 Ð Processor Module (PSIO)
|
| LEGEND | |
COMM | Ð | Communications Bus | NO Ð Normally Open |
NC | Ð | Normally Closed | PWR Ð Power |
Fig. 21 Ð Low-Voltage Relay Module (DSIO)