Table 10 Ð Operational and Mode Display Codes
The operating modes are displayed by name or code num- ber, to indicate the operating status of the unit at a given time. The modes are:
CODE | DESCRIPTION |
| |
| Unit is off. |
| |
LOCAL OFF | OFF position, or | ||
may be in LOCAL position with external ON/OFF | |||
| |||
| switch in OFF position. | ||
|
| ||
CCN OFF | Unit is off due to CCN network command. LOCAL/ |
| |
| |||
CLOCK OFF | Unit is off due to internal clock schedule. LOCAL/ |
| |
| |||
LOCAL ON | Unit is on. |
| |
LOCAL position. If external ON/OFF switch is used, | |||
| it will be in ON position. | ||
CCN ON | Unit is on due to CCN command. LOCAL/ENABLE- |
| |
| |||
CLOCK ON | Unit is on due to internal clock schedule or occu- |
| |
pied override function. | |||
| CCN switch is in LOCAL/ENABLE position. | ||
| Dual set point is in effect. In this mode, unit contin- |
| |
MODE 7 | ues to run in unoccupied condition, but leaving ¯uid | ||
set point is automatically increased to a higher level | |||
| |||
| (CSP2 set point is in SET function). | ||
|
| ||
| Temperature reset is in effect. In this mode, unit is |
| |
| using temperature reset to adjust leaving ¯uid set | ||
MODE 8 | point upward, and unit is currently controlling to the | ||
modi®ed set point. The set point can be modi®ed based | |||
| |||
| on return ¯uid, | ||
| perature. | ||
| Demand limit is in effect. This indicates that ca- |
| |
MODE 9 | pacity of unit is being limited by demand limit control | ||
option. Because of this limitation, unit may not | |||
| be able to produce the desired leaving ¯uid | ||
| temperature. | ||
MODE 10 | Flotronic™ System Manager (FSM) is controlling the |
| |
chiller. | |||
| |||
MODE 11 | Not applicable. |
| |
| Ramp load (pulldown) limiting is in effect. In this mode, |
| |
| the rate at which leaving ¯uid temperature is dropped | ||
MODE 12 | is limited to a predetermined value to prevent com- | ||
pressor overloading. See CRAMP set point in the | |||
| SET function in Table 9. The pulldown limit can be | ||
| modi®ed, if desired, to any rate from .2 F to 2 F | ||
| (.1° to 1° C)/minute. | ||
| Timed override is in effect. This is a 1 to 4 hour tem- |
| |
MODE 13 | porary override of the programmed schedule, forc- | ||
ing unit to occupied mode. Override can be imple- | |||
| mented with unit under LOCAL/ENABLE or CCN | ||
| control. Override expires after each use. | ||
| Low cooler suction protection is in effect. In this mode, |
| |
| circuit capacity is not allowed to increase if cooler | ||
| saturated suction temperature is 20° F (11° C) for | ||
MODE 14 | ¯uid or 30° F (16° C) for brine or more below leaving | ||
¯uid temperature, and saturated suction tempera- | |||
| |||
| ture is less than 32 F (0° C). If these conditions per- | ||
| sist beyond 10 minutes, circuit is shut down and fault | ||
| code 44 or 45 is displayed. | ||
MODE 15 | Water System Manager is controlling the chiller. |
| |
MODE 16 | Slow change override is in effect. |
| |
MODE 17 | X minute |
| |
MODE 18 | Low suction superheat protection is in effect. |
|
CCN Ð Carrier Comfort Network
(Set Point) Ð This subfunction displays leaving
¯uid temperature and leaving chilled ¯uid set point. If unit is programmed for dual set point, the chilled ¯uid set point currently in effect (either occupied or unoccupied) is displayed. If reset is in effect, the unit operates to the modi- ®ed chilled ¯uid set point. This means the leaving ¯uid tem- perature may not equal the chilled ¯uid set point. The modi®ed chilled ¯uid set point can also be displayed in the Status function. To enter the set point subfunction,
press and press to display the set point fol-
lowed by the modi®ed leaving chilled ¯uid set point and ac- tual control temperature.
(Temperature) Ð The temperature subfunction dis- plays the readings at temperature sensing thermistors.
To read a temperature, enter , then scroll to de-
sired temperature using the | key. See Table 9 for the |
order of readouts. This subfunction also displays the satu- rated refrigerant temperatures corresponding to the suction and discharge pressures measured by the compressor transducers.
(Pressure) Ð This subfunction displays suction,
discharge, and net oil pressure at lead compressor of each circuit of unit.
(Analog Inputs) Ð This subfunction displays
analog inputs, if any. Press , then press . The
transducer supply voltage,
(Discrete Inputs) Ð This subfunction displays sta-
tus (open/closed) of discrete input switch where applicable. Status of dual set point switch and demand limit switches 1 and 2 can be displayed. This is useful for problem diagnosis prior to using the test function.
(Outputs) Ð This function displays on/off sta-
tus of alarm relay, all fan relays, and chilled water pump relay. It also displays on/off status of compressor unloaders (if used). The position of each EXV (in percent open) can be displayed.
TEST FUNCTION Ð The test function operates the diag- nostic program. To initiate test function, the LOCAL/
To reach a particular test, press its subfunction number,
then scroll to desired test by pressing . Press to
start a test. Press or or to terminate or exit a
test. Pressing the key after a test has started advances
system to next test, whether current test is operating or has timed out. Once in the next step, you may start
test by pressing or advance past it by pressing .
While the unit is in test, you may leave test function and access another display or function by pressing appropriate keys. However, a component that is operating when an- other function is accessed remains operating. You must
ponent. Components with a timed operating limit time out normally even if another function is accessed.
37