TRANSDUCER REPLACEMENT

Fig. 17 Ð Lead Compressor Transducer and Thermistor Locations

TRANSDUCER REPLACEMENT

Transducers are installed directly in the refrigerant cir- cuit. Relieve all refrigerant pressure using standard re- frigeration practices before removing.

1.Relieve refrigerant pressure using standard refrigeration practices.

2.Disconnect transducer wiring at transducer by pulling up on locking tab while pulling weathertight connection plug from end of transducer. Do not pull on transducer wires.

3.Unscrew transducer from 1¤4-in. male ¯are ®tting. When installing new pressure transducer, do not use thread sealer. Thread sealer can plug transducer and render it inoperative.

4.Insert weathertight wiring plug into end of transducer un- til locking tab snaps in place.

5.Check for refrigerant leaks.