Carrier 30GN040-420 Example 4 Ð Reading and Changing, Chilled Fluid Set Point, Ð Reset Amounts

Models: 30GN040-420

1 72
Download 72 pages 43.68 Kb
Page 39
Image 39
Example 4 Ð Reading and Changing

Example 4 Ð Reading and Changing

Chilled Fluid Set Point

KEYPAD

DISPLAY

COMMENTS

ENTRY

RESPONSE

 

 

 

SET POINT

System set points

 

 

CSP1 44.0

Present occupied chilled ¯uid

 

 

set point is 44.0 F

 

 

CSP1 42.0

Press the

.

 

 

 

 

Display shows new occupied

 

 

chilled ¯uid set point is 42.0 F

 

CSP2 44.0

Present unoccupied chilled ¯uid

 

set point is 44.0 F

 

 

 

 

 

CSP2 50.0

Press the

. Display

 

 

 

 

shows new unoccupied chilled

 

 

¯uid set point is 50.0 F

 

RESET

Displays the maximum reset

 

 

set point. The minimum and

 

 

maximum reference reset

 

 

set points can also be displayed.

 

 

These set points are not

 

 

accessible when reset type has

 

 

been con®gured for NONE in

 

 

the service function.

 

 

 

 

 

Subfunction displays temperature reset set points.

Temperature Reset Based on Return Fluid Temperature Ð The control system is capable of providing leaving ¯uid tem- perature reset based on return ¯uid temperature. Because the temperature difference between leaving and return tempera- ture is a measure of the building load, return ¯uid tempera- ture reset is essentially an average building load reset method.

Under normal operation, the chiller maintains a constant leaving ¯uid temperature approximately equal to chilled fluid set point. As building load drops from 100% down to 0%, entering cooler ¯uid temperature drops in proportion to load. Thus, temperature drop across the cooler drops from a typi- cal 10 F (5.5 C) at full load to a theoretical 0° F (0° C) at no load. See Fig. 5.

At partial load, leaving chilled ¯uid temperature may be lower than required. If this is allowed to increase (reset), the efficiency of the chiller increases. Amount of reset can be de®ned as a function of cooler temperature drop, as shown in Fig. 5. This is a simple linear function that requires 3 pieces of input data for the set function that will vary de- pending on measurement method used as follows (see Table 11):

NOTE: Reset set points are not accessible unless the reset function is enabled ®rst. This is done as a ®eld

con®guration. Select one of the 4 choices for type of reset: Return Fluid Reset, External Temperature Reset, 4-20 mA External Signal Reset, or 4-20 mA Internal Signal Reset.

If dual set point control is enabled (see Field Wiring sec- tion on page 69), the amount of reset is applied to whichever set point is in effect at the time.

Examples 5A-5C demonstrate how to activate reset. Ex- ample 6 demonstrates how to change the type of reset. As- sume that reset is to be based on return ¯uid temperature, the desired reset range is to be 0° to 10° F (0° to 5.5° C) and full load is a 10° F (5.5° C) drop across the cooler. See Fig. 5.

Activating reset based on external temperature or 4-20 mA signal is done the same way, except the reference set point range is ±40° to 240° F (±40° to 115° C), or 4 to 20 mA depending on which method was selected at the ®eld con®guration step.

Example 5A Ð External Reset

In this example, the unit set point is reset from full load at 90 F (32 C) to a maximum reset value of 10 F (5.5 C) at 20 F (±6.7 C) outdoor ambient.

NOTE: All temperatures given in this example are in F.

KEYPAD

DISPLAY

COMMENTS

ENTRY

RESPONSE

 

 

 

 

 

FLD CFG

 

 

CRTYP 0

Scroll past to reset type

 

CRTYP 2

External reset selected

 

ERTYP 0

Scroll past to space

 

thermistor sensor selected

 

 

 

ERTYP 1

OAT selected

 

RESET

 

 

CRT2N 0

Temperature for no

 

reset is 0

 

 

 

CRT2N 90

Temperature for no

 

reset is 90

 

 

 

CRT2F 0

Temperature for maximum

 

reset is 0

 

 

 

CRT2F 20

Temperature for maximum

 

reset is 20

 

 

 

CRT2D 0

Maximum reset is 0

 

CRT2D 10

Maximum reset is 10

 

 

 

Table 11 Ð Reset Amounts

 

 

 

MEASUREMENT METHOD

 

 

INPUT DATA DESCRIPTION

4-20 mA

OAT/Occupied Space

Return Water

or Internal/External

 

 

 

 

 

 

Variable

Limits (F)

Variable

Limits (F)

Variable

Limits (F)

Maximum Reset Amount Ð Allowable range for

CRT1

±30 to 30

CRT2D

±30 to 30

CRT3D

±30 to 30

maximum amount which LWT is to be reset.

 

 

 

 

 

 

Maximum Reset Reference Ð Temperature at

Ð

Ð

CRT2F

±40 to 240

CRT3F

0 to 15

which maximum reset occurs.

 

 

 

 

 

 

Minimum Reset Reference Ð Temperature at

Ð

Ð

CRT2N

±40 to 240

CRT3N

0 to 15

which no reset occurs.

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

OAT Ð Outdoor-Air Temperature

 

 

 

 

 

 

LWT Ð Leaving Fluid Temperature

 

 

 

 

 

 

39

Page 39
Image 39
Carrier 30GN040-420 Example 4 Ð Reading and Changing, Chilled Fluid Set Point, Example 5A Ð External Reset