Carrier 30GN040-420 operating instructions Disconnect transducer from the system

Models: 30GN040-420

1 72
Download 72 pages 43.68 Kb
Page 60
Image 60
1.Disconnect transducer from the system.

LEGEND

DPT Ð Discharge Pressure Transducer

EXV Ð Electronic Expansion Valve

OPT Ð Oil Pressure Transducer

SPT Ð Suction Pressure Transducer

T Ð Thermistor Number

Fig. 14 Ð Thermistor and Pressure Transducer Locations

Pressure Transducers Ð A single style of pressure transducer is used for both high- and low-pressure sensing on Flotronic™ II chillers. However, this transducer must be calibrated before the unit will operate. On new units, this will have been done at the factory in order to test run the unit. If a transducer or PSIO is replaced in the ®eld, how- ever, the transducer will have to be ®eld calibrated as follows:

1.Disconnect transducer from the system.

2.Hang the transducer in the atmosphere.

3.Press Manual backgroundon the HSIO keypad, and Read the pres- sure. Pressures before calibration must be within the range of 6 5 psig. If the pressure is outside the range of 6 5 psig, the HSIO display will read ---. If this is the case, replace the transducer or PSIO or check for a wir- ing error. If the value of the atmospheric pressure is greater than 5 psig or less than ±5 psig, the transducer will be considered out of range and will not calibrate.

4. Press Manual background on the HSIO keypad. This automatically ap-

plies the proper correction factor to all future inputs from the transducer.

Three pressure transducers are mounted on each lead com- pressor: 2 low-pressure transducers to monitor compressor suction pressure and oil pressure, and a high-pressure trans- ducer to monitor compressor discharge pressure (see Fig. 17 for exact locations on compressor). Each transducer is supplied with 5 vdc power from a recti®er which changes 24 vac to 5 vdc.

TROUBLESHOOTING Ð If transducer is suspected of be- ing faulty, ®rst check supply voltage to transducer. Supply voltage should be 5 vdc ± .2 v. If supply voltage is correct, compare pressure reading displayed on keypad and display module against pressure shown on a calibrated pressure gage. If the 2 pressure readings are not reasonably close, replace pressure transducer.