Keypad and Display Module
Controls, Operation, and Troubleshooting
ACCESSORY UNLOADER INSTALLATION
30GN040-420
Table 1 Ð Unit Sizes and Modular Combinations
SAFETY CONSIDERATIONS
GENERAL
MAJOR SYSTEM COMPONENTS
LEGEND CCN Ð Carrier Comfort Network
Fig. 1 Ð 30GN Control Panel 040-110Unit Shown
TB Ð Terminal Block
Keypad and Display Module Also Called HSIO
Table 3 Ð Thermistor and Transducer Locations
Fig. 3 Ð Compressor Ground Fault Module
Compressor Protection Control Module CPCS
OPERATION DATA
Table 4A Ð Capacity Control Steps
Table 4A Ð Capacity Control Steps, 040-070cont
Table 4A Ð Capacity Control Steps, 040-070cont
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
UNIT
LOADING SEQUENCE A
LOADING SEQUENCE A
A1*,B1
LOADING SEQUENCE A
A1,kB1
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
LOADING SEQUENCE A
Fig. 4 Ð Keypad and Display Module
Head Pressure Control
Pumpout
Keypad and Display Module Also Called HSIO
Table 5 Ð Condenser Fan Sequence
Table 7 Ð Functions and Subfunctions
Table 6 Ð Keypad and Display Module Usage
Table 9 Ð Keypad Directory STATUS
Table 8 Ð Accessing Functions and Subfunctions
KEYPAD ENTRY
6 TEMPERATURE
Table 9 Ð Keypad Directory cont STATUS cont
SUBFUNCTION
DISPLAY
Table 9 Ð Keypad Directory cont STATUS cont
SUBFUNCTION
KEYPAD ENTRY
TEST
Table 9 Ð Keypad Directory cont STATUS cont
SCHEDULE
Table 9 Ð Keypad Directory cont TEST cont
Table 9 Ð Keypad Directory cont SCHEDULE cont
SERVICE
Table 9 Ð Keypad Directory cont SERVICE cont
KEYPAD ENTRY
3 ALARM/ALERT
Table 9 Ð Keypad Directory cont HISTORY
SUBFUNCTION
Table 9 Ð Keypad Directory cont SET POINT
Example 2 Ð Reading Current Operating Modes
Example 1 Ð Reading Alarm Codes
Table 10 Ð Operational and Mode Display Codes
Pulldown Set Point
Example 3 Ð Using Test Function
Reset Set Points
Chilled Fluid Set Point
Chilled Fluid Set Point
Example 5A Ð External Reset
Table 11 Ð Reset Amounts
Example 4 Ð Reading and Changing
Example 5B Ð 4 to 20 mA and Internally or
Externally Powered Reset
Example 5C Ð Using Return Fluid Temperature Reset
Fig. 5 Ð Cooling Return Fluid Reset
COMM Ð Communications Bus
Fig. 6 Ð Cooling External Temperature Reset
Ð Power
Ð Switch
Externally powered
Fig. 8 Ð 4-20mA Cooling Temperature Reset
Example 6 Ð Changing Reset Type
Table 12 Ð Service Functions
First Log On As Shown in Table
To Disable Demand Limit
Example 7B Ð Using Demand Limit 4-20mA
Example 8 Ð Setting Time of Day and Day of Week
Fig. 9 Ð 4-20mA Demand Limiting
and press while on the correct conguration
Table 14 Ð Adjustable Field Congurations
Table 13 Ð Factory Conguration Keystrokes
To change a conguration enter the new conguration
Example 9 Ð Using the Schedule Function cont
Example 9 Ð Using the Schedule Function
Example 10 Ð Holiday Schedule Function
TROUBLESHOOTING
Fig. 10 Ð Sample Time Schedule
Cooling load satised
Table 16 Ð Alarm and Alert Codes
Table 16 Ð Alarm and Alert Codes cont
Fig. 11A Ð 24-VSafety Circuit Wiring
Code 30 Reset input failure 4 to 20 mA alert
Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vac supplying the PSIO, DSIO-LV,or 4 IN/4 OUT the 12.5-vactrans- former supplying the DSIO-EXVmodule, or the 24-vactrans- former supplying PS1 for the transformers. These transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are not grounded
Code 42 Cooler freeze protection alarm
Fig. 12 Ð Electronic Expansion Valve EXV
Electronic Expansion Valve EXV
Module, DSIO EXV
Fig. 13 Ð EXV Cable Connections to EXV Driver
6.Check operation of EXV
TEMPERATURE
TEMPERATURE
1.Disconnect transducer from the system
Fig. 15 Ð Thermistor Locations
FLUID-SIDETEMPERATURE THERMISTOR T2
COMPRESSOR SUCTION GAS TEMPERATURE
ALL UNITS AND FLUID-SIDETEMPERATURE
TRANSDUCER REPLACEMENT
Control Modules
Fig. 21 Ð Low-VoltageRelay Module DSIO
ACCESSORY UNLOADER INSTALLATION
Fig. 19 Ð Sensor Bus Wiring Communications
Fig. 20 Ð Processor Module PSIO
Fig. 22 Ð 4 In/4 Out Module SIO
Installation
Table 20 Ð Standard and Accessory Unloaders
Table 19 Ð Troubleshooting
The keypad LCD will display
3.Wire in the solenoid valves
pad display reads OUTPUTS. Press until display
Press
See Table
Externally Powered
Switch Inputs
Fig. 26 − Demand Limit Ð 4-20mA Signal
Fig. 30 Ð Remote Reset from 4-20mA Signal
Fig. 35 Ð Interlocks
Installation
Fig. 34 Ð Remote Alarm
REPLACING DEFECTIVE PROCESSOR MODULE
Page
Copyright 1995 Carrier Corporation