Carrier 30GN040-420 operating instructions Ð Condenser Fan Sequence

Models: 30GN040-420

1 72
Download 72 pages 43.68 Kb
Page 25
Image 25
Table 5 Ð Condenser Fan Sequence

Table 5 Ð Condenser Fan Sequence

FAN ARRANGEMENT

FAN NUMBER(S)

FAN CONTACTOR

CONTROLLED BY

30GN

(FC)

 

 

040-050

1

FC-A1

Compressor A1

 

 

 

 

 

2

FC-B1

Compressor B1

 

3

FC-A2

First Stage

 

Microprocessor

 

 

 

 

4

FC-B2

Second Stage

 

Microprocessor

 

 

 

060,070

1

FC-A1

Compressor A1

 

 

 

 

 

2

FC-B1

Compressor B1

 

 

 

 

 

3, 4

FC-A2

First Stage

 

Microprocessor

 

 

 

 

5, 6

FC-B2

Second Stage

 

Microprocessor

 

 

 

080,090 (and associated modular units*)

1

FC-A1

Compressor A1

 

2

FC-B1

Compressor B1

 

 

 

 

 

3

FC-A2

First Stage

 

 

 

 

4

FC-B2

Microprocessor

 

 

 

 

 

 

 

3, 4, 5, 6

FC-A2, FC-B2,

Second Stage

 

FC-A3, FC-B3

Microprocessor

 

 

100,110 (and associated modular units*)

1

FC-A1

Compressor A1

 

 

 

 

 

2

FC-B1

Compressor B1

 

 

 

 

 

3

FC-A2

First Stage

 

4

FC-B2

Microprocessor

 

 

 

 

 

 

 

5, 7, 6, 8

FC-A3, FC-B3

Second Stage

 

Microprocessor

 

 

 

 

3, 4, 5, 6, 7, 8

FC-A2, FC-A3,

Third Stage

 

FC-B2, FC-B3

Microprocessor

 

 

130-170 (and associated modular units*)

5, 7

FC-A1

Compressor A1

 

6, 8

FC-B1

Compressor B1

 

 

 

 

 

3, 9

FC-A2

First Stage

 

4, 10

FC-B2

Microprocessor

 

 

 

 

 

 

 

1, 3, 9

FC-A2, FC-A3

Second Stage

 

 

 

 

2, 4, 10

FC-B2, FC-B3

Microprocessor

 

 

190,210 (and associated modular units*)

5, 7

FC-A1

Compressor A1

 

 

 

 

 

6, 8

FC-B1

Compressor B1

 

 

 

 

 

3, 9

FC-A2

First Stage

 

 

 

 

4, 10

FC-B2

Microprocessor

 

 

 

 

 

 

 

1, 3, 9, 11

FC-A2, FC-A3

Second Stage

 

2, 4, 10, 12

FC-B2, FC-B3

Microprocessor

 

 

 

 

 

 

*See Table 1. ²Control box.

AUTOMATIC DISPLAY OPERATION/DEFAULT DIS- PLAY Ð This display automatically rotates as follows:

DOW Ð Day of Week

HHÐ Hour(s)

MM Ð Minute(s)

The default rotating display is displayed every 2 seconds if there has been no manual input from the keypad for 10 minutes.

To return to automatic display, enter Manual background at any time.

KEYPAD OPERATING INSTRUCTIONS (Refer to Table 9.)

1.White keys on left side of keypad are shown and oper- ated in these instructions according to the following ex-

ample: keypad entry Manual background means press the Manual background , then

the white key marked Manual background .

2.The standard display uses abbreviations. Expanded in-

formation scrolls through the display whenever Manual background key is pressed.

25

Page 25
Image 25
Carrier 30GN040-420 operating instructions Ð Condenser Fan Sequence