Carrier 30GN040-420 operating instructions Ð Keypad Directory cont SET POINT

Models: 30GN040-420

1 72
Download 72 pages 43.68 Kb
Page 35
Image 35
Table 9 Ð Keypad Directory (cont)

Table 9 Ð Keypad Directory (cont)

SET POINT

To read a set point, go to proper subfunction and read desired set point. To change a set point, enter new set point value, then press

.

LOCAL/ENABLE-STOP-CCN switch must be in LOCAL/ENABLE or STOP position.

 

 

 

 

 

 

SUBFUNCTION

KEYPAD ENTRY

DISPLAY

COMMENT

 

 

 

 

 

 

1 SET POINTS

 

SET POINT

Unit Set Point

 

 

 

CSP1 X

Chiller Fluid Set Point 1 (F)

 

 

 

CSP2 X

Chiller Fluid Set Point 2 (F)

 

 

 

HSPA X

Head Pressure Set Point Circuit A (F)

 

 

 

HSPB X

Head Pressure Set Point Circuit B (F)

 

 

 

CRAMP X

Cooling Ramp Loading Rate (F)

 

 

 

 

 

 

2 RESET SET POINTS

 

RESET

Reset Set Points

 

 

 

CRT1 X

Cooling reset at 20 mA (F)

 

 

 

CRT2N X

Reference Temperature at No Reset (F)

 

 

 

CRT2F X

Reference Temperature at Full Reset (F)

 

 

 

CRT2D X

Total Degrees of Reset (F)

 

 

 

CRT3N X

Chiller Fluid DT at No Reset (F)

 

 

 

CRT3F X

Chiller Fluid DT at Full Reset (F)

 

 

 

CRT3D X

Total Degrees of Reset (F)

 

 

 

 

 

 

3 DEMAND SET POINTS

 

DEMAND

Demand Set Points

 

 

 

DLS1 X²

Demand Switch 1 Set Point (percent)

 

 

 

DLS2 X²

Demand Switch 2 Set Point (percent)

 

 

 

DL20 X

Demand Limit at 20 mA (percent)

 

 

 

DLGN X

Loadshed Group Number

 

 

 

LSDD X

Loadshed Demand (percent)

 

 

 

TIME X

Minimum Loadshed Time (minutes)

 

 

 

 

 

 

4 DATE AND TIME

 

DATE.TIME

Date, Time and Day of Week

 

 

 

DOW.HR.MIN

Day 1 = Mon, 2 = Tues. . .7 = Sun

 

 

 

 

Hours are displayed in 24-hr time. Decimal point serves as colon.

 

 

 

MM.DD.YR

Month.Day.Year. When entering date, enter a decimal

 

 

 

 

point between entries. Each entry must be two numbers.

 

 

 

 

 

 

5 LEAVING CHILLER

 

LMT X

Leaving Chiller Fluid Alert Limit (F)

 

FLUID ALERT LIMIT

 

 

 

 

 

 

LEGEND

CCN Ð Carrier Comfort Network

EXV Ð Electronic Expansion Valve

MOP Ð Maximum Operating Pressure

*Will read ALARM or ALERT as appropriate. ²Must be con®gured.

**If applicable.

²²Not manually resettable.

NOTE: If metric option is selected under Manual background , temperature expressed as Celsius and pressure will be expressed as kPa.