Carrier 30GN040-420 operating instructions

Models: 30GN040-420

1 72
Download 72 pages 43.68 Kb
Page 53
Image 53
Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vac supplying the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5-vac trans- former supplying the DSIO-EXV module, or the 24-vac trans- former supplying PS1 for the transformers. These transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are not grounded.

 

LEGEND

 

CB

Ð Circuit Breaker

 

CGF

Ð

Ground Fault Module

 

COMM

Ð Communications Bus

 

CR

Ð Compressor Contactor Relay

 

DSIO

Ð

Relay Module (Low Voltage)

*And associated modular units.

HPS

Ð

High-Pressure Switch

 

LV

Ð

Low Voltage

 

PL

Ð

Plug

 

SNB

Ð

Snubber

 

TB

Ð

Terminal Block

 

TRAN

Ð

Transformer

 

U

Ð Unloader

 

Fig. 11C Ð 24-V Safety Circuit Wiring (130-210 and Associated Modular Units)

Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vac supplying the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5-vac trans- former supplying the DSIO-EXV module, or the 24-vac trans- former supplying PS1 for the transformers. These transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are not grounded.

Code 36 Low refrigerant pressure, Circuit A (alert) Code 37 Low refrigerant pressure, Circuit B (alert)

If suction pressure transducer senses a pressure below set point for more than 5 minutes at start-up or more than 2 minutes during normal operation, affected circuit shuts down without going through the pumpout process. Reset is auto- matic when pressure reaches 10 psig above set point if there have been no previous occurrences of this fault on the same day. If this is a repeat occurrence on same day, then reset is manual, with LOCAL/ENABLE-STOP-CCN switch. Fac- tory con®gured set point is 27 psig for standard chillers and 12 psig for brine chillers.

Possible causes of fault are low refrigerant charge, faulty EXV, plugged ®lter drier, or faulty transducer.

Code 38 Failure to pump out, Circuit A (alert) Code 39 Failure to pump out, Circuit B (alert)

The pumpout process is terminated when saturated suc- tion temperature is 10° F (5.6° C) below temperature at be- ginning of pumpout, or 10° F (5.6° C) below leaving water temperature or reaches a saturated suction temperature of ±15 F (±26 C). If appropriate saturated suction temperature is not met within 3 minutes (on 2 consecutive tries), circuit shuts down without pumpout. Reset is manual with LOCAL/ ENABLE-STOP-CCN switch, and start-up follows normal sequence.

Possible causes for this alarm are a bad thermistor or trans- ducer or a faulty expansion valve.

Code 40 Low oil pressure, Circuit A (alert) Code 41 Low oil pressure, Circuit B (alert)

53

Page 53
Image 53
Carrier 30GN040-420 operating instructions