Carrier 30GN040-420 Ð Keypad Directory cont STATUS cont, Subfunction, Keypad Entry, Display

Models: 30GN040-420

1 72
Download 72 pages 43.68 Kb
Page 28
Image 28
Table 9 Ð Keypad Directory (cont)

Table 9 Ð Keypad Directory (cont)

STATUS (cont)

SUBFUNCTION

KEYPAD ENTRY

DISPLAY

COMMENT

 

 

 

 

4 STAGE

 

STAGE

Capacity Staging Information

 

 

COOL X

Number of Requested Stages

 

 

CAPT X

Percent of Total Capacity

 

 

CAPA X

Percent Circuit A Total Capacity

 

 

CAPB X

Percent Circuit B Total Capacity

 

 

AVAIL X

Percent Available Capacity

 

 

AV A X

Percent Circuit A Available Capacity

 

 

AV B X

Percent Circuit B Available Capacity

 

 

LMT X²

Demand Limit Set Point (percent)

 

 

CIRA X

Circuit A Compressor Relay Status

 

 

CIRB X

Circuit B Compressor Relay Status

 

 

SMZ X

Load/Unload Factor for Compressors

 

 

 

Factor = 1 Unloader Factor = 0.6

 

 

 

 

5 SET POINT

 

SETPOINT

Fluid Set Point Information

 

 

SET X

Set Point (F)

 

 

MSP X

Modi®ed Set Point = Set Point + Reset (F)

 

 

TW X

Actual Control Temperature (F)

 

 

 

 

6 TEMPERATURE

 

TEMPS

Temperature Information (F)

 

 

EWT X

Cooler Entering Fluid Temperature (F)

 

 

LWT X

Cooler Leaving Fluid Temperature (F)

 

 

SCTA X

Circuit A Saturated Condenser Temperature (F)

 

 

SSTA X

Circuit A Saturated Suction Temperature (F)

 

 

CTA X

Compressor A1 Suction Temperature (F)

 

 

SHA X

Circuit A Suction Superheat (F)

 

 

SCTB X

Circuit B Saturated Condenser Temperature (F)

 

 

SSTB X

Circuit B Saturated Suction Temperature (F)

 

 

CTB X

Compressor B1 Suction Temperature (F)

 

 

SHB X

Circuit B Suction Superheat (F)

 

 

SPC X

Space Temperature (F)

 

 

OAT X

Outdoor-Air Temperature (F)

 

 

 

 

LEGEND

CCN Ð Carrier Comfort Network

EXV Ð Electronic Expansion Valve

MOP Ð Maximum Operating Pressure

*Will read ALARM or ALERT as appropriate. ²Must be con®gured.

**If applicable.

²²Not manually resettable.

NOTE: If metric option is selected under 4 STAGE , temperature expressed as Celsius and pressure will be expressed as kPa.

28

Page 28
Image 28
Carrier 30GN040-420 Ð Keypad Directory cont STATUS cont, Subfunction, Keypad Entry, Display, Comment, Stage, Set Point