TEST

Table 9 Ð Keypad Directory (cont)

STATUS (cont)

SUBFUNCTION

KEYPAD ENTRY

DISPLAY

COMMENT

 

 

 

 

10 OUTPUTS (cont)

 

EXVB X

EXVB Percent Open**

 

 

HGBA X²

Hot Gas Bypass Relay Circuit A (on/off)**

 

 

HGBB X²

Hot Gas Bypass Relay Circuit B (on/off)**

 

 

MMA X²

Motormaster A Output Percent**

 

 

MMB X²

Motormaster B Output Percent**

 

 

 

 

 

 

TEST

 

 

 

 

 

To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position. To operate a test, scroll to desired test.

Then, press Manual background to start test. Press Manual background to stop test.

SUBFUNCTION

KEYPAD ENTRY

 

 

DISPLAY

COMMENT

 

 

 

 

 

 

1 OUTPUTS

 

 

 

OUTPUTS

Test Outputs

 

 

 

 

8.8.8.8.8.8.8.8

Display Check

 

 

 

 

ALMR X

Energize Alarm Relay K3 (on/off)

 

 

 

 

FRA1 X

Energize Fan Relay A1 K1 (on/off)

 

 

 

 

FRA2 X

Energize Fan Relay A2 K2 (on/off)

 

 

 

 

FRB1 X

Energize Fan Relay B1 K4 (on/off)

 

 

 

 

FRB2 X

Energize Fan Relay B2 K5 (on/off)

 

 

 

 

CHWP X²

Energize Cooler Water Pump K6 (on/off)

 

 

 

 

LSVA X

Energize Liquid Line Solenoid A (on/off)**

 

 

 

 

LSVB X

Energize Liquid Line Solenoid B (on/off)**

 

 

 

 

EXVA X

Enter Desired EXVA Position (percent)**

 

 

 

 

EXVB X

Enter Desired EXVB Position (percent)**

 

 

 

 

HGBA X²

Energize Hot Gas Bypass Relay A (on/off)**

 

 

 

 

HGBB X²

Energize Hot Gas Bypass Relay B (on/off)**

 

 

 

 

MMA X²

Enter Desired Motormaster A Output Signal (percent)**

 

 

 

 

MMB X²

Enter Desired Motormaster B Output Signal (percent)**

 

 

 

 

 

 

To toggle between inputs (Yes/No) Press:

(no) or

(yes)

 

 

 

 

 

 

 

During compressor test, compressors start and run for 10 seconds. Compressor service valves and liquid line valves must be open. Energize crankcase heaters 24 hours prior to performing compressor tests.

SUBFUNCTION

KEYPAD ENTRY

DISPLAY

COMMENT

 

 

 

 

2 COMPRESSORS AND

 

COMP

Compressor and Unloader Test

UNLOADERS

 

 

 

 

 

 

CPA1 X

Test Compressor A1 (on/off)

 

 

CPA2 X²

Test Compressor A2 (on/off)**

 

 

 

 

30

Page 30
Image 30
Carrier 30GN040-420 operating instructions Ð Keypad Directory cont STATUS cont, Test