SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo- nents, and equipment location (roof, elevated structures, etc.). Only trained, quali®ed installers and service mechanics should install, start up, and service this equipment.
When working on this equipment, observe precautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Fol- low all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
This unit uses a
GENERAL
IMPORTANT: This publication contains controls, op- eration and troubleshooting data for
Circuits are identi®ed as circuits A and B, and com- pressors are identi®ed as A1, A2, etc. in circuit A, and B1, B2, etc. in circuit B.
Use this guide in conjunction with separate Instal- lation Instructions booklet packaged with the unit.
The 30G Series standard Flotronic II chillers feature
NOTE: The 30GN040 and 045 chillers with a factory- installed brine option have thermal expansion valves (TXV) instead of the EXV.
Unit sizes
Table 1 Ð Unit Sizes and Modular Combinations
UNIT MODEL | NOMINAL | SECTION A | SECTION B |
30GN | TONS | UNIT 30GN | UNIT 30GN |
040 | 40 | Ð | Ð |
045 | 45 | Ð | Ð |
050 | 50 | Ð | Ð |
060 | 60 | Ð | Ð |
070 | 70 | Ð | Ð |
080 | 80 | Ð | Ð |
090 | 90 | Ð | Ð |
100 | 100 | Ð | Ð |
110 | 110 | Ð | Ð |
130 | 125 | Ð | Ð |
150 | 145 | Ð | Ð |
170 | 160 | Ð | Ð |
190 | 180 | Ð | Ð |
210 | 200 | Ð | Ð |
230 | 220 | 150 | 080 |
245 | 230 | 150 | 090 |
255 | 240 | 150 | 100 |
270 | 260 | 170 | 100 |
290 | 280 | 190 | 110 |
315 | 300 | 210 | 110 |
330 | 325 | 170 | 170 |
360 | 350 | 190 | 190/170* |
390 | 380 | 210 | 190 |
420 | 400 | 210 | 210 |
|
|
|
|
*60 Hz units/50 Hz units.
The Flotronic II control system cycles compressor un- loaders and/or compressors to maintain the selected leaving ¯uid temperature set point. It automatically positions the EXV to maintain the speci®ed refrigerant superheat entering the compressor cylinders. It also cycles condenser fans on and off to maintain suitable head pressure for each circuit. Safe- ties are continuously monitored to prevent the unit from op- erating under unsafe conditions. A scheduling function, pro- grammed by the user, controls the unit occupied/unoccupied schedule. The control also operates a test program that al- lows the operator to check output signals and ensure com- ponents are operable.
The control system consists of a processor module (PSIO), a
MAJOR SYSTEM COMPONENTS
Processor Module Ð This module contains the oper- ating software and controls the operation of the machine. It continuously monitors information received from the vari- ous transducers and thermistors and communicates with the relay modules and