Chapter 3 Installing the Router

Supplemental Bonding and Grounding Connections

Figure 3-4 Supplemental Bonding and Grounding Port for NEBS

Compliance

GIGABIT ROUTE PROCESSOR

CISCO 12000

GIGABIT SWITCH ROUTER

57744

Use a dual-hole lug to connect to the chassis with two 6.3-mm (M6) screws on the 0.63-inch (16-mm) centers as shown in Figure 3-4and Figure 3-5. The lug can be ordered from Cisco (Part Number 32-0607-01).

Figure 3-5

Cable Lug

2.24

End View

 

 

 

 

 

Ø 0.267

 

 

 

 

 

0.48

 

 

 

2 holes

 

 

 

 

 

 

 

 

 

 

 

0.25 0.63 0.37 0.08

All measurements in inches

Crimp area

25527

The dual-hole lug is crimped onto a grounding wire of a wire size and length determined by your router location and facility environment. The crimping tool shown in Figure 3-6is a standard crimping tool obtainable from many sources.

 

Cisco 12006 and Cisco 12406 Router Installation and Configuration Guide

3-10

OL-11497-03

Page 10
Image 10
Cisco Systems 12006, 12406 manual Supplemental Bonding and Grounding Port for Nebs Compliance