Appendix A Cabinet and Rack Installation
Cisco MDS 9000 Family Telco and EIA Shelf Bracket
Requirements Specific to Solid-Walled Cabinets
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on page
•A
•Nonperforated (solid and sealed) front and back doors and side panels so that air travels predictably from bottom to top.
•The overall cabinet depth should be 36 to 42 in. (91.4 to 106.7 cm) to allow the doors to close and adequate airflow.
•A minimum of 150 sq. in. (968 sq. cm) of open area at the floor air intake of the cabinet.
•The lowest piece of equipment should be installed a minimum of 1.75 in. (4.4 cm) above the floor openings to prevent blocking the floor intake.
Requirements Specific to Standard Open Racks
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on page
•Width between two front mounting rails: minimum of 17.75 in. (45.1 cm)
•Minimum vertical rack space per chassis: 1 rack unit (RU), equal to 1.75 in. (4.4 cm)
•The distance between the outside face of the front mounting rail and the outside face of the back mounting rail should be 23.5 to 34.0 in. (59.7 to 86.4 cm) to allow for rear bracket installation.
•The distance between the chassis air vents and any walls should be 2.5 in. (6.4 cm).
Requirements Specific to Telco Racks
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on page
•The width of the rack between the two
•The distance between the chassis air vents and any walls should be 2.5 in. (6.4 cm).
Cisco MDS 9000 Family Telco and EIA Shelf Bracket
The optional telco and EIA Shelf Bracket Kit (part number
This kit supports the following configurations:
•A Cisco MDS 9100 Series switch in a
•A Cisco MDS 9100 Series switch in a
Cisco MDS 9100 Series Hardware Installation Guide
|
| |
|