Conair MPW Press the up key to begin calibrating, Wait until the control displays “don” or “bad.”

Models: MPW MPA

1 86
Download 86 pages 25.93 Kb
Page 55
Image 55
6 Press the up ▲ key to begin calibrating.

6 Press the up key to begin calibrating.

The controller displays the name of the current calibration (examples: 32 SC.L; 32 rC.L; 510 SC.H; or 510 rC.H).

7 Wait until the control displays “don” or “bad.”

A “don” message in the Setpoint display indicates the cali- bration was successful. A “bad” message in the Setpoint display indicates a bad calibration.

NOTE: The original calibration value stored in EEProm can be restored for the current calibration by pressing the STOP key at any time.

8

Press Select

 

to start the next calibration.

 

Pressing and releasing the Select 7 Wait until the control displays “don” or “bad.” key at the end of a calibration tells the controller to perform the next calibra- tion.

9 Exit Calibration Mode.

Press and hold the Select Press Select key for 3 seconds to exit the Calibration Mode.

You can now proceed to the next test in Test Mode, or disable Test Mode and resume normal operation.

TO DISABLE TEST MODE, complete steps 2 through 5 in PERFORMING SYSTEM TESTS, setting dip switch 6 to OFF instead of ON.