The chiller has detected a problem that could lead to equipment damage or personal injury if it is not corrected.

The Alarm LED lights and the STOP/RUN LED flashes red.

The chiller automatically shuts down.

The control displays a red LED or alarm code indicating the source of the problem.

SHUT DOWN ALARMS

Alarm

Possible cause Solution

Lo SAF

Actual temperature of water supplied to the process is below the programmed 10° F safety limit.

Has the compressor contactor failed closed?

Has the unloader valve failed?

Has the freezestat failed?

Check phase continuity through the compressor con- tactor. If the contactor has failed, replace it. See

REPLACING THE COMPRESSOR CONTACTOR.

See CHECKING THE UNLOADER

VALVE.

Check the freezestat setting. It should be set to cut out at 5° F above the freeze point of the process fluid solution.

Check for improper freezes- tat installation. Verify the freezestat sensor bulb is

well insulated and inserted into the piping well.

If the freezestat is properly installed and set, it may have

failed See REPLACING THE

FREEZESTAT.

Pbr

Err

Is the thermocouple

Check for a loose thermocou-

loose?

ple or loose wire connections

 

to the thermocouple.

The thermocouple

 

 

 

in the process

Has the thermocouple

Check the thermocouple and

return line failed.

failed?

replace if necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the thermocouple

Check for a loose thermocou-

 

 

 

 

 

 

 

 

 

 

 

PbS

 

 

 

Err

 

 

 

 

 

 

 

 

 

loose?

ple or loose wire connections

 

 

 

 

 

 

 

 

 

The thermocouple

 

to the thermocouple.

 

 

 

 

 

 

in the process

Has the thermocouple

Check the thermocouple and

supply line failed.

failed?

replace if necessary.