The chiller has detected a problem that could lead to equipment damage or personal injury if it is not corrected.
◆The Alarm LED lights and the STOP/RUN LED flashes red.
◆The chiller automatically shuts down.
◆The control displays a red LED or alarm code indicating the source of the problem.
SHUT DOWN ALARMS
Alarm | Possible cause Solution |
Lo SAF
Actual temperature of water supplied to the process is below the programmed 10° F safety limit.
Has the compressor contactor failed closed?
Has the unloader valve failed?
Has the freezestat failed?
Check phase continuity through the compressor con- tactor. If the contactor has failed, replace it. See
REPLACING THE COMPRESSOR CONTACTOR.
See CHECKING THE UNLOADER
VALVE.
❒Check the freezestat setting. It should be set to cut out at 5° F above the freeze point of the process fluid solution.
❒Check for improper freezes- tat installation. Verify the freezestat sensor bulb is
well insulated and inserted into the piping well.
If the freezestat is properly installed and set, it may have
failed See REPLACING THE
FREEZESTAT.
Pbr
Err
Is the thermocouple | Check for a loose thermocou- |
loose? | ple or loose wire connections |
| to the thermocouple. |
The thermocouple |
|
|
| ||||||||
in the process | Has the thermocouple | Check the thermocouple and | |||||||||
return line failed. | failed? | replace if necessary. | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Is the thermocouple | Check for a loose thermocou- | |
|
|
|
|
|
|
|
|
| |||
|
| PbS |
|
|
| Err |
|
| |||
|
|
|
|
|
|
| loose? | ple or loose wire connections | |||
|
|
|
|
|
|
|
|
| |||
The thermocouple |
| to the thermocouple. | |||||||||
|
|
| |||||||||
|
|
| |||||||||
in the process | Has the thermocouple | Check the thermocouple and | |||||||||
supply line failed. | failed? | replace if necessary. |
UGH004/0999 | microKool Portable Chiller | TROUBLESHOOTING |