PHS  Err

SHUT DOWN ALARMS

The chiller has detected a problem that could lead to equipment damage or personal injury if it is not corrected.

The Alarm LED lights and the STOP/RUN LED flashes red.

The chiller automatically shuts down.

The control displays a red LED or alarm code indicating the source of the problem.

Alarm

Possible cause Solution

PHS Is the pump rotating in the wrong direction?Manual background Err

The incoming power is out of phase. A leg may have failed or is disconnected.

Is the pump rotating in the wrong direction?

Check pump rotation against the arrow stamped on the pump. If the pump is rotating in the wrong direction, discon- nect and lockout the main power source. Open the electri- cal enclosure, and reverse

any two leads on the power connection.

NOTE: This alarm is available only on PC-2 models.

Has one of the main sup-

Disconnect power and open

ply wire leads become

the electrical enclosure. Check

disconnected?

for loose connections in main

 

supply and on motherboard.

 

 

FUS Manual backgroundManual background 002

Pump fuse.

FUS Manual backgroundManual background 003

Compressor fuse.

FUS Manual backgroundManual background 004

Unloader valve fuse.

FUS Manual backgroundManual background 005

Unloader valve fuse.

FUS Manual backgroundManual background 006

Level Switch fuse.

Has the indicated device

Disconnect and lockout the

blown a fuse?

main power. Open the electri-

 

cal enclosure. Check for loose

 

wires and incorrectly installed

 

jumpers or terminal blocks

 

associated with the fuse error.

 

Replace the fuse, if necessary.

 

See CHECKING AND REPLACING

 

FUSES.

 

 

Is the correct device

Replace the fuse, then enter

being used for this fuse

Test Mode. Turn off the Output

location?

Monitor associated with the

 

fuse location and test outputs.

 

See PERFORMING SYSTEM TESTS

 

and DISABLING OR ENABLING

 

OUTPUT MONITORS in the

 

MAINTENANCE section.

 

 

Has the motherboard

Replace the motherboard. See

output channel at the

REPLACING THE MOTHERBOARD.

designated fuse failed?

 

6-6

TROUBLESHOOTING