Conair MPA, MPW Calibrating Temperature Sensors, 5-12, Enable Test Mode, Release the Setpoint key

Models: MPW MPA

1 86
Download 86 pages 25.93 Kb
Page 54
Image 54
CALIBRATING

CALIBRATING

TEMPERATURE

SENSORS

Special Tools Needed:

thermocouple calibrator

The microKool chillers use thermocouples to sense the tem- perature in the return and supply process lines. These thermo- couples should be calibrated annually, or when a new thermo- couple is installed, to ensure correct operation.

The chiller’s Calibration Mode provides zero and span calibra- tion of both the supply and return line thermocouples. You access the Calibration Mode while in Test Mode.

1 Enable Test Mode.

See PERFORMING SYSTEM TESTS.

2 Press any button to display the first test menu. 3 Select the Calibration Mode menu.

Press and hold the Setpoint Special Tools Needed: key for 3 seconds to index to each test menu until the controller indicates “SC.L” in the Actual display.

4

Release the Setpoint ❒thermocouple calibrator key.

You are now in calibration mode. Each press and release of this key will exit the current calibration and start the next calibration. The table below lists the calibrations that will be performed.

 

SETPOINT

ACTUAL

CALIBRATION

DISPLAY

DISPLAY

Zero Calibrate Supply Sensor

32° F (0° C)

SC.L

 

 

 

Zero Calibrate Return Sensor

32° F (0° C)

rC.L

 

 

 

Span Calibrate Supply Sensor

510° F (266° C)

SC.H

 

 

 

Span Calibrate Return Sensor

510° F (266° C)

rC.H

 

 

 

5

Using the thermocouple calibrator, apply the appropriate temperature to the control input.

5-12

MAINTENANCE

microKool Portable Chillers

UGH004/0999

Page 54
Image 54
Conair MPA, MPW Calibrating Temperature Sensors, 5-12, Enable Test Mode, Release the Setpoint key, Special Tools Needed