TESTING THE INSTALLATION
NOTE: Make sure the chiller tank is full of process fluid before you begin operating.
|
|
|
|
| WARNING: Only qualified personnel | ||||
|
|
|
|
| should perform this procedure. |
|
| ||
|
|
|
|
| Parts of this test require opening the unit while it is | ||||
|
|
|
|
| energized. Only qualified personnel who have been | ||||
|
|
|
|
| trained in the use of electrical testing devices and | ||||
|
|
|
|
| in avoiding the safety hazards involved in safely | ||||
|
|
|
|
| troubleshooting this type of equipment should per- | ||||
|
|
|
|
| form this test procedure. |
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
| Turn on the condenser water supply (MPW | |||||
| 1 | ||||||||
|
|
|
| units) and check for leaks. If any leaks appear, stop | |||||
|
|
|
| the test and fix the problem before continuing. The water | |||||
|
|
|
| pressure must be at least must be at least 25 PSI at the | |||||
|
|
|
| condenser inlet. |
|
| |||
|
|
|
| Apply power to the unit. |
|
| |||
| 2 |
|
|
| |||||
|
|
|
| ◆ Indicator lights on the control panel blink green, then | |||||
|
|
|
|
| red, to test operation of the LEDs. |
|
| ||
|
|
|
| ◆ Setpoint and actual windows will display |
|
| for | ||
|
|
|
|
| three seconds, followed by the software version. The | ||||
|
|
|
|
| windows then display the factory default setpoint of | ||||
|
|
|
|
| 50° F (10° C) and the actual temperature. |
|
| ||
|
|
|
|
|
|
|
| ||
| 3 |
|
| Check the rotation of the pump. Remove the | |||||
|
|
|
| access panel and verify that the pump rotation matches the | |||||
|
|
|
| direction indicated on the rotation stamp on the pump. | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| NOTE: If the rotation is incorrect, stop the test and |
|
| |||
|
|
|
| disconnect power to the unit. Open the electrical |
|
| |||
|
|
|
| enclosure and switch any two of the three power |
|
| |||
|
|
|
| source wires on the terminal block. Return to Step 2 |
| ||||
|
|
|
| and check rotation again. |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 4 |
|
| Replace the access panel. |
|
| |||
|
|
|
| Press the RUN key to start the unit. |
|
| |||
| 5 |
|
|
|
|
If everything is working correctly: ◆ The RUN/STOP light turns green.
◆ The pump begins operating. The compressor turns on after 3 seconds, if the actual temperature is above the setpoint.
◆ Normal operation begins. The unloader valves turn on, if the actual temperature is below setpoint. The com- pressor remains active until the actual temperature is 6° F below the setpoint.
The test is over. Proceed to initial setup if the unit operated normally; refer to the TROUBLESHOOTING section if it did not.
INSTALLATION | microKool Portable Chillers | UGH004/0999 | |
|
|