SHUT DOWN ALARMS
The chiller has detected a problem that could lead to equipment damage or personal injury if it is not corrected.
◆The Alarm LED lights and the STOP/RUN LED flashes red.
◆The chiller turns off the compressor, but normal operation resumes after you clear the alarm or the problem corrects itself.
◆The control displays a red LED or alarm code indicating the source of the problem.
Alarm | Possible cause Solution |
Refrigerant Pressure
Refrigerant pressure is either too low or too high.
WARNING:
The microKool should be tested and repaired only by qualified techni- cians equipped with the correct tools and trained in the mainte- nance and repair of electrical and refriger- ant systems used in industrial applications.
Low refrigerant pressure:
Is the refrigerant charge low?
Is the liquid refrigerant line restricted?
High refrigerant pressure
Has the water or air flow through the condenser become restricted?
(Continued on next page)
See CHECKING REFRIGERANT
CHARGE. Check for leaks in the refrigerant circuit. Contact a certified refrigerant technician to repair and recharge the sys- tem.
Check for closed valves or a plugged refrigerant line.
❒Verify that the liquid line
❒Verify that the suction valve at the compressor is open.
❒Verify that the expansion valve is working properly.
Check for closed valves and obstructions, contaminants or dirt that may have blocked or restricted condenser efficiency.
All models:
❒Clean the condenser coils. See
CLEANING CONDENSERS.
Air-cooled units:
❒Remove any obstructions to air flow at the condenser air inlet and outlet.
❒Verify that the condenser fans are working. Confirm proper rotation and check for an elec- trical overload.
Water-cooled units:
❒Check for closed valves or plugged water supply lines.
❒Verify that the condenser water supply is working and that incoming water pressure is at least 25 psi.
TROUBLESHOOTING | microKool Portable Chillers | UGH004/0999 |