SHUT DOWN ALARMS

SHUT DOWN ALARMS

The chiller has detected a problem that could lead to equipment damage or personal injury if it is not corrected.

The Alarm LED lights and the STOP/RUN LED flashes red.

The chiller turns off the compressor, but normal operation resumes after you clear the alarm or the problem corrects itself.

The control displays a red LED or alarm code indicating the source of the problem.

Alarm

Possible cause Solution

Refrigerant pressure is either too low or too high. Refrigerant Pressure

Refrigerant pressure is either too low or too high.

Low refrigerant pressure: WARNING:

The microKool should be tested and repaired only by qualified techni- cians equipped with the correct tools and trained in the mainte- nance and repair of electrical and refriger- ant systems used in industrial applications.

Low refrigerant pressure:

Is the refrigerant charge low?

Is the liquid refrigerant line restricted?

High refrigerant pressure

Has the water or air flow through the condenser become restricted?

(Continued on next page)

See CHECKING REFRIGERANT

CHARGE. Check for leaks in the refrigerant circuit. Contact a certified refrigerant technician to repair and recharge the sys- tem.

Check for closed valves or a plugged refrigerant line.

Verify that the liquid line shut-off valve is open.

Verify that the suction valve at the compressor is open.

Verify that the expansion valve is working properly.

Check for closed valves and obstructions, contaminants or dirt that may have blocked or restricted condenser efficiency.

All models:

Clean the condenser coils. See

CLEANING CONDENSERS.

Air-cooled units:

Remove any obstructions to air flow at the condenser air inlet and outlet.

Verify that the condenser fans are working. Confirm proper rotation and check for an elec- trical overload.

Water-cooled units:

Check for closed valves or plugged water supply lines.

Verify that the condenser water supply is working and that incoming water pressure is at least 25 psi.

6-8

TROUBLESHOOTING

microKool Portable Chillers

UGH004/0999