ENABLING AND

DISABLING

PASSCODE

PROTECTION

WARNING: Electric shock hazard

This equipment is powered by high voltage. Always disconnect and lock out the main power source before opening the unit or the electrical enclosure to modify factory settings. Failure to disconnect and lock out the main power source can result in severe personal injury.

The PC-1 and PC-2 controls provide the ability to protect sys- tem parameters from unauthorized changes during normal operating mode. When system passcode protection is enabled, the following parameters cannot be changed unless you enter the correct passcode:

The Process Setpoint

High Deviation Alarm Setpoint

Low Deviation Alarm Setpoint

Baud Rate selection for serial communications

Address selection for serial communications

When the unit is turned on for the first time, passcode protec- tion is disabled. To enable passcode protection:

1

Disconnect and lock out main power to the unit.

2

Open the electrical enclosure.

 

3

Set dip switch 3 to ON

8 7 6 5 4 3 2 1

 

and switches 5 and 6

 

 

to OFF.

 

4

Close the electrical enclosure and restore

 

power to the unit.

 

5

Press any

 

 

button when

 

 

the control dis-

 

 

plays “Pas rSt”

 

 

(Passcode Reset).

 

 

The control will

 

 

display the last

 

 

passcode used.

 

6

Select a new passcode using the and

 

setpoint adjustment buttons.

 

 

Stop pressing the setpoint buttons when the passcode you

 

want appears in the setpoint display window. Selecting

 

“OFF” as the passcode will disable the passcode feature.

3-10

INSTALLATION

microKool Portable Chillers

UGH004/0999

Page 26
Image 26
Conair MPA, MPW manual Enabling Disabling Passcode Protection, Disconnect and lock out main power to the unit