bell Options

Bell Options

10.1

BELL OPTIONS

Bell Options

This section allows you to program the panel bell output functions.

10.2

BELL CUTOFF: 15

Bell Cutoff Time

Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the area is disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell output. The default is 15 minutes.

Note: To support the Alarm Verify feature on an All/Perimeter or Home/Sleep/Away system, set the Bell Cutoff Time to greater than 0.

Note: For SIA CP-01 False Alarm Reduction Installations, the Bell Cutoff Time must be set to a minimum of six (6) minutes.

10.3

10.4

Automatic Bell Test

Bell tst No YES Select YES to turn on the Bell Output for 2 seconds each time the system is completely­ armed from a keypad. This test is delayed until the Closing Wait acknowledge is received (if programmed). If the Closing Wait acknowledge is not received within 90 seconds, the bell test does not occur. Arming performed from an Arming zone or from Remote Link™ does not activate the Bell Test.

 

 

Bell Output

 

 

Bell outPUT:

0

Enter the output number when needed to follow the panel Bell Output operation for

 

 

all action and off conditions. Enter 0 (zero) to disable.

 

 

 

 

Note: When BELL ACTION is set to T for Temporal Code 3, the Bell Output action for

 

 

an LX-Bus output is pulse.

10.5

Bell ACTION . . . . .

Bell Action

This section defines the type of Bell Output for zone alarms. Press COMMAND to display the default Bell Output for each zone type. Press any Select key and enter S for a Steady Bell Output, P for a Pulsed output, T for a Temporal Code 3 output, and N for no Bell Output.

Note: Trouble conditions do not activate the Bell Output.

10.5.1

10.5.2

10.5.3

10.5.4

10.5.5

10.5.6

10.5.7

 

 

 

Fire Bell Action

 

 

 

Fire

Type:

p

Defines Bell Action for Fire Type zones. The default is P.

 

 

 

Burglary Bell Action

 

 

 

 

 

 

Burglary Type:

S

Defines Bell Action for Burglary Type zones and Exit Error output. The default is S.

 

 

 

Supervisory Bell Action

 

 

 

 

 

 

Suprvsry Type:

N

Defines Bell Action for Supervisory Type zones. The default is N.

 

 

 

Panic Bell Action

 

 

 

 

 

 

Panic

Type:

N

Defines Bell Action for Panic Type zones. The default is N.

 

 

 

Emergency Bell Action

 

 

 

 

 

 

Emergncy Type:

N

Defines Bell Action for Emergency Type zones. The default is N.

 

 

 

Auxiliary 1 Bell Action

 

 

 

 

 

 

Auxlry 1 Type:

N

Defines Bell Action for Auxiliary 1 Type zones. The default is N.

 

 

 

Auxiliary 2 Bell Action

 

 

 

 

 

 

Auxlry 2 Type:

N

Defines Bell Action for Auxiliary 2 Type zones. The default is N.

 

 

 

 