XR500 Series Canadian Programming Guide Digital Monitoring Products
17
deviCe SeTuP
6.6
DISPLAY AREAS:
Display Areas
*1 *2 *3 *4
*5 *6 *7 *8
*9 *10 *11 *12
*13 *14 *15 *16
*17 *18 *19 *20
*21 *22 *23 *24
*25 *26 *27 *28
*29 *30 *31 *32
PresstheCOMMANDkeytoprogramDisplayAreas.Toselectanareabetween1and
32,entertheareanumberusingthekeypaddigitkeys.Whenanareaisselected,an
asterisk appears next to the area number. Enter the number again to deselect the
area.PressCOMMANDtodisplaythenextsetofareas.Defaultisallareanumbers.
Refer to the Multiple Displays section at the beginning of this document.
Display Areas allows the XR500 Series burglary activities to be segmented so that
onlyspecicarea(s)andtheirassociatedoperationappearataparticularkeypad.
Areanumber(s)selectedinthiseldaffectthewayusersinteractwiththesystem
from this particular device. For example: Program Device 1 to show only the zone
activities and armed status of Area 1.
Entertheareanumber(s)thatthiskeypadistodisplay.Thisallowsspecicareacontrol
fromspecickeypads,aswellasannunciationofzonesassignedtothosearea(s).When
DisplayAreasisleftdefaulted(allareasselected),MenuDisplayandStatusListitems
determine whether zone alarms and troubles display at this device, regardless of area
assignment. Also, all system areas may be armed and disarmed from this device.
Note: For an All/Perimeter or Home/Sleep/Away system, Display Areas should be
left at factory default settings.
ForHome/Sleep/AwaywithGuestarmingsystems,theDisplayAreasselection
determineswhichsystemthekeypadarmsanddisarms.Withareas1,2or3being
therstareasselected,thekeypadisassignedtotheMainsystem.Witharea4,5or6
beingtherstareasselected,thekeypadisassignedtotheGuest1system.Witharea
7,8or9beingtherstareasselected,thekeypadisassignedtotheGuest2system.
KeypadscanhaveadditionalareasassignedforEventDisplay.
User Action Allowed
Whenanarea(s)isselected,thefollowinguseractionsareallowed:
• ArmingorDisarmingofthearea(s)selectedfromtheARMorDISARMmenu
• AlarmSilenceforthearea(s)selected
• ZoneBypassofzonesassignedtothearea(s)selected
• ZoneMonitorofzoneassignedtothearea(s)selected
• Shiftschedulechangesallowedforthearea(s)selected
• ClosingCheckScheduleExtendisallowedforthearea(s)selected
• DoorScheduleschangesareallowedfordevicesthathaveamatchingarea(s)
 asdenedinDeviceAccessAreas
• DoorOn/OffMenuoperationisallowedfordevicesthathaveamatchingarea(s)
 asdenedinDeviceAccessAreas
Note:Theprevioususeractionsalsorequirethematchingarea(s)beprogrammedin
UserProle:Arm/Disarmarea(s).
Status Display Allowed
Whenanarea(s)ischosen,thefollowingdisplaysareallowed:
• ArmedStatusoftheselectedarea(s)
• ZoneAlarmsandtroublesforburglary(NT,DY,EX,A1,A2)typezonesassignedto
 theselectedarea(s)
• LatetoClosestatusoftheselectedarea(s)
• ZoneStatus(normal/fault)ofzonesthatareassignedtotheselectedarea(s)
Options and Actions Not Affected
The following options are not affected by the Display Areas operation. The User
Code authority level controls access to these items.
•SensorResetMenu •OutputsOn/OffMenu •SystemStatusMenu
•SystemTest/PanicTest•UserProles •ForgiveAnti-Passback
•ServiceRequest •SetSystemTimeandDate
•FireDrill •DisplayEvents
•24-hourzonesdisplayatkeypadsbasedonStatusListprogrammingonly
Note:Acommonareaanditsoperationscannotbeassignedtoaspecickeypad.
DisplayAreasexample:WhenDevice1hasDisplayAreassetto20,21,and22,it
annunciates troubles and alarms only for zones assigned to those areas.
Whenarming/disarmingfromDevice1,onlyareas20,21,and22maybearmed/
disarmed,evenwhentheUserProlehasauthoritytoarm/disarmothersystemareas.
Exception: Disarming of other areas not selected in Display Areas can be
accomplishedbypresentingacardthathasdisarmingauthorityandmatchingprole
areas with areas assigned in Device Access Areas.