DMP Electronics XR500 19.9, Next Zone, DMP Wireless, 19.10.1 19.10.2, Serial Number Entry

Models: XR500

1 84
Download 84 pages 63.88 Kb
Page 60
Image 60

19.9

Next Zn? No YES

Zone Information

Next Zone

Select YES to terminate zone programming. The display returns to Zone Number, allowing you to enter a new zone number. Select NO to make alter­ations to the Alarm Action for a zone. Alarm Action is defined beginning with section 16.12.

To program zones for wireless operation, select NO at the NEXT ZONE - NO YES option. The WIRELESS NO YES option displays. If the zone you are programming is intended for wireless devices, select YES. Select NO to continue programming nonwireless zones in the 500 to 999 range.

Zones 400 to 449 can be programmed for 1100 Series Key Fobs.

Zones 500 to 699 can be programmed for FA Series Wireless.

Zones 500 through 999 can be programmed for DMP 1100 Series Wireless.

DMP Wireless

For a DMP 1100X Wireless Receiver set the House Code from 1 to 50. See House Code programming in System Options. Zones 500 through 999 can be programmed as Wireless zones. Set the XR500 Series Canadian panel J23 jumper to X to enable on-board DMP Wireless operation. Briefly reset the panel using the J16 jumper to activate Wireless operation. Refer to the XR500 Series Canadian Installation Guide (LT-0681).

For an 1100 Series Key Fob see section 19.11.

For an FA Series Remote Wireless Receiver see section 19.12.

NOTE: All wireless programming is stored in the XR500 Series Canadian panel. The 1100X Wireless Receiver obtains the necessary programming information from the panel each time the receiver powers up, when the programmer STOP routine is selected or the panel is reset. The receiver memory refresh takes up to 10 seconds to complete depending on the number of wireless zones programmed and the Red LED remains on during this time. Normal receiver operation is inhibited during the memory refresh period.

19.10

zone information wireless? no yes

Wireless

Select YES to program this zone as a DMP wireless zone. You must program the wireless House Code prior to adding DMP wireless zones to the system. See House Code programming in System Options. Default is NO.

19.10.1

19.10.2

TRANSMITTER sERIAL#: XXXXXXXX

ALREADY IN USE ZONE NUMBER: XXX

TRANSMITTER CONTACT:XXXXXXXX

Serial Number Entry

Enter the eight-digit serial number found on the wireless device.

This message displays when the serial number is already programmed for another zone. The programmed zone number displays.

Contact

This option displays if the serial number entered is for an 1101 or 1103 Universal Transmitter or 1114 Wireless Four-Zone Expander. Press any top row key to select the contact.

TRANSMTR CONTACT INT EXT

This option displays when programming an 1101 or 1103 Transmitter. Select INT to use the internal reed switch contacts. Select EXT to connect an external device to the 1101 or 1103 terminal block. Default is INTERNAL.

By allowing both of the Model 1101 or 1103 transmitter contacts (INT and EXT) to be used at the same time, two zones may be programmed from one transmitter. When using both contacts, you must use consecutive zone numbers. Zones 531 and 532 or zones 890 and 891 are acceptable zone assignments.

For example, program transmitter serial number 01345678 as Zone 521 with an INT contact type and Zone 522 with an EXT contact type. The same serial number is used for both zones.

XR500 Series Canadian Programming Guide

Digital Monitoring Products

51

Page 60
Image 60
DMP Electronics XR500 manual 19.9, Next Zone, DMP Wireless, 19.10.1 19.10.2, Serial Number Entry, Contact