Status List

Display Keypads:

System Troubles:

Fire Zones:

Status List

Status List

Status List

This function allows you to select the zone alarms and troubles, and system monitor troubles displayed at the keypads. The Status List function operates automatically when the keypad is not performing any other function.

The keypad stays in the Status List until the user arms or disarms or selects a menu option. Status List al­ternates with the Armed Status on keypad addresses selected in the Menu Display - Armed Status section. You can choose to have Sys­tem Monitor troubles placed in the list, the differ­ent zone types placed in the list, and at which keypad addresses they dis­play.

To select a keypad, enter the device number (keypad address) using the digit keys on the keypad. When a keypad is selected, an asterisk appears next to the keypad address. Enter the number again to deselect the keypad. Press the COMMAND key to display the next set of keypads (9 through 16). Refer to the Multiple Displays section at the beginning of this document.

Display Keypads

This option defines which keypad ad­dresses display the various status information. Any combina­tion of addresses can be en­tered to display the status items that follow. If you do not want a particular status item to dis­play, do not enter any ad­dresses.

System Monitor Troubles

Specifies the keypad addresses (1 through 16) where any trouble on a System Monitor displays­. The System Monitors include the following:

AC Power

Battery Power

Closing Check

Panel Box Tamper

Phone Line 1

Phone Line 2 (requires the 893A Dual Phone Line Module)

Wireless Receiver Trouble

Wireless Jamming Trouble or Alarm

The System Monitor name is placed in the Status List and the keypad steady trouble buzzer sounds. The buzzer remains on until any keypad top row Select key is pressed. The name remains in the list until the condition is re­stored. The buzzer sounds at 10:00 am daily until the system trouble is cleared from the Status List.

Fire Zones

Specifies the keypad addresses (1 through 16) where all fire zone alarms and troubles display. The zone name displays and, if it is a trouble condition, the keypad steady trouble buzzer sounds. The buzzer remains on until any top row Select key is pressed and a user code is entered. If a trouble condition remains in the display, the buzzer sounds at 10:00 am daily until the trouble is cleared from the Status List.

When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire:

On - Fire zone alarm and Bell Output or Fire Bell Output is ON.

Off - Alarm Silence

XR500 Series Canadian Programming Guide

Digital Monitoring Products

39