11.1
output Options
Output Options
Output Options
Output Options
This section allows you to program panel output options. The panel provides two Form C relays (1 and 2) and four switched ground (open collector) outputs numbered 3 to 6. Expand the system up to 500 additional relay outputs using J22
Select from the following output numbers:
•1 to 6
•450 to 474 — Slow response time* wireless outputs (activates within 15 seconds)
•480 to 499 — Fast response time* wireless outputs (activates within 1 second)
•500 to 999 —
•D1 to D16 — Keypad door strike relay for addresses
•G1 to G20 — Output group
*The response time of a wireless output is the time it takes for a wireless output to activate once the panel event occurs. You determine whether a wireless output is a slow or fast response based on the output number assigned. A slow response output number extends battery life, but response time may be up to 15 seconds. A fast response output number responds within 1 second, but reduces battery life. Refer to the specific wireless output installation guide to determine battery life.
11.2.1
Co outs: - - - - - -
Cutoff Output
Outputs 1 to 6 can be entered here to turn off after a time specified in CUTOFF TIME. To disable this option, press any Select key to clear the display then press COMMAND. The Cutoff Output displays dashes when no outputs are selected.
11.2.2
Cutoff time: 0
Output Cutoff Time
If a Cutoff Output
11.3
Comm trbl out: 0
Communication Trouble Output
Enter the output number to turn on when a DD system fails to communicate on three successive dial attempts or if the backup communication line transmits a report. The Communication Trouble Output also turns on when NET is selected as the primary communication method and NET communication fails after one minute. When NET communication is restored the Communication Trouble Output automatically turns off.
To manually turn the output off, disarm any area or select Off for the output number in the User Menu Outputs On/Off section. Enter 0 (zero) to disable this output.
11.4
Fire alr out: | 0 |
|
|
Fire Alarm Output
Enter the output number to turn on when a fire type zone is placed in alarm. The output is turned off using the Sensor Reset option while no additional fire type zones are in alarm. Enter 0 (zero) to disable. This output is not compatible with Cutoff Outputs.
11.5
Fire trb out: 0
Fire Trouble Output
Enter the output number to turn on when a fire type zone is placed in trouble, when a supervisory type zone is placed in alarm or trouble, or when any system monitor (AC, Battery, Phone Line 1 or Phone Line 2) is placed in trouble. The output turns off when all fire and supervisory type zones, or system monitors are restored to normal. Enter 0 (zero) to disable this output. This output is not compatible with Cutoff Outputs. This output can be connected to a lamp, LED, or buzzer using the DMP Model 716 Output Expansion Module.
XR500 Series Canadian Programming Guide | Digital Monitoring Products |
33