Digital Monitoring Products XR500 Series Canadian Programming Guide
56
zone informaTion
FA Series Wireless
For an FA Series Remote Wireless ReceiversettheHouseCodeto99.SeeHouseCodeprogrammingin
SystemOptions.Onlyzones500to699canbeprogrammedasFASeriesWirelesszonesformaximumof
200WirelessZones.
For a DMP 1100X Wireless Receiver see section 16.10.
19.12
ZONE INFORMATION
WIRELESS? NO YES
Wireless
SelectYEStoprogramawirelesszoneconnectedtoanFASeriesFA400-DMPRemote
WirelessReceiver.PresstheCOMMANDkeytocontinuewithwirelessprogramming.
19.12.1
CHECK IN TM: 60
Check-in Time
Youcansetwirelesstransmitterstocheckinautomaticallyevery10,30,or60
secondsornotatall.Tochangethe60seconddefault,pressanytoprowSelect
keytodisplayNONE103060.Selectthecheck-intimeyouwantforthiszone.
Note:RefertotheWirelessCheck-inandSupervisionTimeDenitionssectionof
the Appendix for supervision information.
19.12.2
INT CONT NO YES
Internal Contact
SelectYEStouseaninternalcontactonthewirelesstransmitter.SelectNO
touseanexternalcontact.WhenyouselectNO,thefollowingtwoprompts
display.
19.12.3
EOL NO YES
End-of-Line
Select YES to supervise an external contact connected to the wireless
transmitter.Atthecontact,installa2.2kOhmEnd-of-Lineresistorinparallel
forNormallyOpencontactsandinseriesforNormallyClosedcontacts.
19.12.4
NRM OPEN NO YES
Normally Open
SelectNOifthecontactconnectedtothewirelesstransmitterisNormally
Closed.
19.12.5
NEXT ZONE NO YES
Next Zone
SelectYEStoreturntotheZONENO:-prompttoprogramanewzone.Select
NOtodisplaytheAlarmActionoption.
19.13
ALARM ACTION . . . .
Alarm Action
ThisoptionallowsyoutochangeanyZoneTypestandarddenitions.WhentheZone
Typeisspecied,theAlarmActionforthatzoneisstoredinmemory.
IftheZoneTypeisBlank,Night,Day,Exit,Auxiliary1,orAuxiliary2itisa
non-24-hourzoneandtheAlarmActionprogramingbeginswithDisarmedOpen.
IftheZoneTypeisFire,Panic,Emergency,orSupervisoryitisa24-hourzonethatis
alwaysarmedandtheAlarmActionprogrammingbeginswithArmedOpen.
TheFireVerifyZoneTypefunctionsthesameasFireType,withthefollowing
exceptions:WhenaFireVerifyzoneinitiatesanalarm,thepanelperformsaSensor
Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the
reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is
repeated and a zone fault report is sent to the receiver.
DoNOTprogramFireVerifyZoneTypesforZoneRetard.
19.14
DISARMED OPEN
Disarmed Open
Denestheactiontakenbythepanelwhenthezoneisopenedwhiletheareais
disarmed.Therearethreeactionstodene:Reporttotransmit,RelayOutputto
activate,andRelayOutputaction.
YoumustalsomaketheseselectionsfortheDisarmedShort,ArmedOpen,andArmed
Shortzoneconditions.PressCOMMANDtocontinue.