Digital Monitoring Products XR500 Series Canadian Programming Guide
56
zone informaTion
FA Series Wireless
For an FA Series Remote Wireless ReceiversettheHouseCodeto99.SeeHouseCodeprogrammingin
SystemOptions.Onlyzones500to699canbeprogrammedasFASeriesWirelesszonesformaximumof
200WirelessZones.
For a DMP 1100X Wireless Receiver see section 16.10.
19.12
ZONE INFORMATION
WIRELESS? NO YES
Wireless
SelectYEStoprogramawirelesszoneconnectedtoanFASeriesFA400-DMPRemote
WirelessReceiver.PresstheCOMMANDkeytocontinuewithwirelessprogramming.
19.12.1
CHECK IN TM: 60
Check-in Time
Youcansetwirelesstransmitterstocheckinautomaticallyevery10,30,or60
secondsornotatall.Tochangethe60seconddefault,pressanytoprowSelect
keytodisplayNONE103060.Selectthecheck-intimeyouwantforthiszone.
Note:RefertotheWirelessCheck-inandSupervisionTimeDenitionssectionof
the Appendix for supervision information.
19.12.2
INT CONT NO YES
Internal Contact
SelectYEStouseaninternalcontactonthewirelesstransmitter.SelectNO
touseanexternalcontact.WhenyouselectNO,thefollowingtwoprompts
display.
19.12.3
EOL NO YES
End-of-Line
Select YES to supervise an external contact connected to the wireless
transmitter.Atthecontact,installa2.2kOhmEnd-of-Lineresistorinparallel
forNormallyOpencontactsandinseriesforNormallyClosedcontacts.
19.12.4
NRM OPEN NO YES
Normally Open
SelectNOifthecontactconnectedtothewirelesstransmitterisNormally
Closed.
19.12.5
NEXT ZONE NO YES
Next Zone
SelectYEStoreturntotheZONENO:-prompttoprogramanewzone.Select
NOtodisplaytheAlarmActionoption.
19.13
ALARM ACTION . . . .
Alarm Action
ThisoptionallowsyoutochangeanyZoneTypestandarddenitions.WhentheZone
Typeisspecied,theAlarmActionforthatzoneisstoredinmemory.
IftheZoneTypeisBlank,Night,Day,Exit,Auxiliary1,orAuxiliary2itisa
non-24-hourzoneandtheAlarmActionprogramingbeginswithDisarmedOpen.
IftheZoneTypeisFire,Panic,Emergency,orSupervisoryitisa24-hourzonethatis
alwaysarmedandtheAlarmActionprogrammingbeginswithArmedOpen.
TheFireVerifyZoneTypefunctionsthesameasFireType,withthefollowing
exceptions:WhenaFireVerifyzoneinitiatesanalarm,thepanelperformsaSensor
Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the
reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is
repeated and a zone fault report is sent to the receiver.
DoNOTprogramFireVerifyZoneTypesforZoneRetard.
19.14
DISARMED OPEN
Disarmed Open
Denestheactiontakenbythepanelwhenthezoneisopenedwhiletheareais
disarmed.Therearethreeactionstodene:Reporttotransmit,RelayOutputto
activate,andRelayOutputaction.
YoumustalsomaketheseselectionsfortheDisarmedShort,ArmedOpen,andArmed
Shortzoneconditions.PressCOMMANDtocontinue.