Installation
Installation of Application Modules
The
NOTE: For programming and operation of the PCM Modules, see "PCX VERSION 6.X OPERATORS" Manual P/N
Figure 32 IOM/PCM Module Connection
PCM Modules I/O Connections
All PCM application modules are equipped with 8 inputs and 4 outputs which are optically isolated for +10 to +30 vdc operation. Each input and output has 2 screw terminals associated with it to provide for either sinking or sourcing operation. The first 8 pairs of designated terminals are inputs and the last 4 pairs of terminals are outputs. The outputs are capable of sinking or sourcing 200 mA. It is the users responsibility to limit the output current to less then or equal to 200 mA.
Adding a
The inputs and outputs allow for proper timing and coordination between the drive's motion and other machine control functions. The inputs and outputs typically are connected to the machine's programmable logic controller (PLC) or