525 Programmable Motion Controller

Figure 13 Differential Input Configuration

Feedback Current

Feedback current (+) and Feedback current (-) are inputs to allow the 525 PMC to monitor the motor current via the voltage proportional to current output on the external drive amplifier. This analog input is scaled at +/-5VDC = continuous current and +/-10VDC = peak current. Fault times range from 4-10 seconds at slightly greater than continuous current to 2-4 seconds at peak current. This is a high impedance input which is referenced to logic ground. Scaling of this input is programmable.

Inputs 1 & 2:

Inputs 1 & 2 allow for external drive's fault indications to be sent to the 525 PMC. A fault on Input 1 will produce a "9" on the display of the 525 PMC and a fault on Input 2 will produce a "11". Polarity of these inputs is programmable. If one or both of these inputs are not used they should have their polarity set at (-) with the "Setup Menu" of PCX (see PCX 6.X manual) or with serial commands. Typical input configuration is shown in 14.

Figure 14 Input Polarity

Drive Enable Outputs

The drive enable outputs allow the 525 PMC to disable the external drive during power up, a bridge inhibit or a fault condition. The output is provided with both normally on and normally off outputs. To utilize the normally on output connect between drive enable (+) and normally on drive enable (-). Consequently, to utilize the normally off output connect between drive enable (+) and normally off drive enable (-). The (+) indicates the collector of an optical isolator while the (-) indicates the emitter.