Operation

Autorestart

When there is a loss of power to the cooling unit and power comes back, the unit will return to its pre- vious operating status—on if it was on before the power off, off if it was off.

When power returns, the autorestart time—time-selectable: Single Unit Auto Restart (Service Menu, Options Setup)—controls the start of the unit. The autorestart time runs in a loop, starting the next unit each time when elapsed, starting with Unit # 1.

Loss of Power Alarm

A Loss of Power Alarm is activated when power is restored after an interruption. If acknowledged, the alarm resets automatically after 30 minutes. This alarm can be set to different event types (Message, Alarm or Warning) and can be disabled under menu item Loss of Power (Service Menu, Set Alarms).

NOTE

Loss of power alarm will be activated only on units that had the fan on before power was lost.

Fan Alarm / Fan Protection Settings

The fan operation is protected by two digital devices: motor protection (optional) and a differential pressure switch. The motor protection monitors for main fan overload and the differential pressure switch ensures that the blower(s) are moving air. If either protection device triggers, an alarm will be announced by a buzzer, alarm relay and event to monitoring after an adjustable time-delay (Main Fan Overload and Loss Of Airflow in Service Menu, Set Alarms).

The time delay at the unit start is always five seconds shorter than the control delay (to avoid short component starting when the fan is not working). During operation, the fan delay is fixed to

15 seconds.

There are two selection possibilities for both, Loss Of Airflow and Main Fan Overload:

Shutdown—stops the unit (intended for DX models).

Disable—stops the humidifier, electrical heaters and dehumidification; allows cooling and free-cooling only (intended for chilled water models / external cooling).

NOTE

When the Main Fan Overload alarm is active, the Loss of Airflow alarm is masked out.

3.1.2Chilled Water Units with Variable Speed Motor

VSD Fan Speed (Auto or Manual VSD Fan Speed Control)

The parameter VSD Fan Speed (Service Menu, Setpoints) allows the cooling unit's fan motor speed to be set for:

Auto operation: when set to Auto, the speed of the VSD (variable speed drive) motor follows the position of the chilled water valve based on predetermined logic for cooling and dehumidification operation.

Manual operation: when set to Manual, the speed of the VSD motor follows user input as set either locally at the cooling unit's Liebert iCOM display (under VSD Setpoint in Service Menu, Setpoints) or remotely using Modbus BMS signal with an optional Liebert IntelliSlot® 485 card.

VSD Setpoint (VSD Fan Speed Setting)

If the VSD Fan Speed Control (Service Menu, Setpoints) is set for Manual, the VSD Fan Speed Set- point (Service Menu, Setpoints) may be set for the desired speed of the variable speed motor.

Depending on the product control design, there may be an internal minimum speed, as defined by that specific product operation, while the customer input may be set for 0-100%:

Fan speed may be set locally at the unit using the Liebert iCOM display.

Fan speed may be set remotely via a BMS signal (sent via Modbus using an optional Liebert Intel- liSlot 485 card), which then transmits to the unit local control.

13

Page 19
Image 19
Emerson iCOM Autorestart, Loss of Power Alarm, Fan Alarm / Fan Protection Settings, VSD Setpoint VSD Fan Speed Setting