Emerson iCOM user manual Delay

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 70
Image 70

Service Menu Parameters

SET

ALARMS

Table 28 Set alarms parameters (continued)

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

Page 2 of 7

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

 

CUST IN1

W

Smoke

 

 

 

Water Alarm

 

 

 

C PMP Alarm

 

 

 

Flow Alarm

 

 

 

Stdby G Pmp

 

 

 

Stdby Unit

 

 

 

C-Input 1

 

 

 

C-Input 2

 

 

 

C-Input 3

 

 

 

C-Input 4

 

 

 

Rht Lockout

 

 

 

Hum Lockout

 

 

 

Rht+Hum Lock

 

 

 

Comp Lockout

 

 

 

Call Service

Customer Input 1

 

 

High Temp

 

 

 

FC Lockout

 

 

 

Air Loss

 

 

 

Heater Alarm

 

 

 

Flow AL SD

 

 

 

Flow AL LC

 

 

 

Comp Lock PD

 

 

 

Enable FC

 

 

 

HTRJ VFD

 

 

 

HTRJ TVSS

 

 

 

Fire Alarm,

 

 

 

2nd Setpoint,

 

 

 

No Power,

 

 

 

LSI,

 

 

 

Cond 1 Fail,

 

 

 

Cond 2 Fail

Customer Input 1 active when

C2 ACT

W

Open, Closed

 

 

 

 

Customer Input 2

CUST IN2

W

Like Custom 2

 

 

 

 

Customer Input 2 active when

C2 ACT

W

Closed, Open

 

 

 

 

Customer Input 3

CUST IN3

W

Like Custom 2

 

 

 

 

Customer Input 3 active when

C3 ACT

W

Closed, Open

 

 

 

 

Customer Input 4

CUST IN4

W

Like Custom 2

 

 

 

 

Customer Input 4 active when

C4 ACT

W

Closed, Open

 

 

 

 

WARNING ACTIVATES ALARM RELAY

WA AC AL

W

No, Yes

 

 

 

 

Reset Disabled Alarms

AL.RES.

W

No, Yes

 

 

 

 

Page 3 of 7

 

 

 

 

 

 

 

PASSWORD

-

W

-

 

 

 

 

DELAY

-

-

-

 

 

 

 

MAIN FAN OVERLOAD

FOL

W

0 - 9999 sec

 

 

 

 

LOSS OF AIRFLOW

LOA

W

0 - 9999 sec

 

 

 

 

CLOGGED FILTERS

CF

W

0 - 9999 sec

 

 

 

 

HIGH ROOM TEMP

HRT

W

0 - 9999 sec

 

 

 

 

LOW ROOM TEMP

LRT

W

0 - 9999 sec

 

 

 

 

HIGH ROOM HUM

HRH

W

0 - 9999 sec

 

 

 

 

LOW ROOM HUM

LRH

W

0 - 9999 sec

 

 

 

 

64