Emerson iCOM user manual Options setup parameters, HUM Steam

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 79
Image 79

Service Menu Parameters

Table 32 Options setup parameters

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

Page 1 of 3

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Compressor Sequence

COMP SEQ

R

Auto, 1, 2

 

 

 

 

Low Pressure Alarm Delay

LP DELAY

W

0-5 min

 

 

 

 

 

 

 

 

 

 

 

 

Electric Stages

EL HEAT

W

0, 1, 2, 3

 

 

 

 

Hot Water Heat On/Off

HW HEAT

W

No, Yes

 

 

 

 

Total Heat Stages

ALL HEAT

R

0, 1, 2, 3

 

 

 

 

LWD Connected

LWDconn

W

No, Yes

 

 

 

 

3P Actuator Runtime

3P RUN

W

30-500 sec

 

 

 

 

3P Actuator Direction

3P DIR

W

Direct, Reverse

 

 

 

 

Page 2 of 3

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Humidification Enabled

HUM ENAB

W

No, Yes

 

 

 

 

Infrared Flush Rate

IR FLUSH

W

110-500%

 

 

 

 

Humidifier Steam Rate

HUM STEAM

W

No, Yes

 

 

 

 

Humidifier Bottle Flush Time

HumFlush

W

5-30 sec

 

 

 

 

Humidifier Bottle Manual Flush

ManFlush

V

Yes, No

 

 

 

 

Auto Restart Enabled

REST EN

W

Yes, No

 

 

 

 

Single Unit Auto Restart

RESTART

W

0-999 sec

 

 

 

 

On-Off Enabled

ONOFF EN

W

Yes, No

 

 

 

 

Page 3 of 3

 

 

 

 

 

 

 

CW Flush

CW FLUSH

W

0-99 hours

 

 

 

 

Freecooling Flush

FC FLUSH

W

0-99 hours

 

 

 

 

Hot Water Flush

HW FLUSH

W

0-99 hours

 

 

 

 

Ball Valve Setpoint Offset

BALL OFF

W

-1.8 / 3.5 bar

(-26 / +51 psi)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

73

Page 79
Image 79
Emerson iCOM user manual Options setup parameters, HUM Steam