Emerson iCOM Two Compressors With Unloaders-Four-Step, Two compressors with unloaders four-step

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 25
Image 25

Operation

Two Compressors With Unloaders—Four-Step

The first two-step compressor is started unloaded at 33% calculated output from the temperature pro- portional band and stopped at 17%. At 80% Compressor 1 will be loaded, at 70% unloaded.

The second compressor starts unloaded at 63% and stops at 47%. At 100%, Compressor 2 will be loaded, at 90% unloaded (see Figure 14).

The four stages of cooling are accomplished in the following manner:

1 stage: One compressor, unloaded - Cool 1

2 stages: Both compressors, unloaded - Cool 2

3 stages: One compressor, loaded and one compressor, unloaded - Cool 3

4 stages: Both compressors, loaded - Cool 4

Figure 14 Two compressors with unloaders (four-step)

Temp Setpoint: 70°F

 

 

Cool 3

Cool 4

 

 

 

On

 

Proportional Band: 8°F

 

 

 

On

 

 

Deadband : 2°F

 

Cool 2

 

 

 

½ Dead-

 

Cool 1

On

 

 

 

 

 

On

 

 

 

 

 

band

 

 

 

 

 

 

 

70

71

72

73

74

 

75

+ 100%

0%

Cool 1

 

 

Cool 3

 

 

 

 

 

 

Cooling

Cooling

Off

Cool 2

Off

Cool 4

 

 

 

Off

 

 

Off

 

½ Proportional Band

Increasing Temperature

19

Page 25
Image 25
Emerson iCOM user manual Two Compressors With Unloaders-Four-Step, Two compressors with unloaders four-step