Service Menu Parameters

SET

ALARMS

Table 28 Set alarms parameters (continued)

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

ENABLE - DISAB

-

-

-

 

 

 

 

COMP 1 OVERLOAD

OL1

W

Disabled, Enabled

 

 

 

 

COMP 2 OVERLOAD

OL2

W

Disabled, Enabled

 

 

 

 

COMP 1 HIGH PRESSURE

HP1

W

Disabled, Enabled

 

 

 

 

COMP 2 HIGH PRESSURE

HP2

W

Disabled, Enabled

 

 

 

 

COMP 1 LOW PRESSURE

LP1

W

Disabled, Enabled

 

 

 

 

COMP 2 LOW PRESSURE

LP2

W

Disabled, Enabled

 

 

 

 

COMP 1 PUMPDOWN FAIL

PD1

W

Disabled, Enabled

 

 

 

 

COMP 2 PUMPDOWN FAIL

PD2

W

Disabled, Enabled

 

 

 

 

DIG SCROLL1 HIGH TEMP

HT1

W

Disabled, Enabled

 

 

 

 

DIG SCROLL2 HIGH TEMP

HT2

W

Disabled, Enabled

 

 

 

 

EL HEAT HIGH TEMP

EHO

W

Disabled, Enabled

 

 

 

 

TYPE

-

-

-

 

 

 

 

COMP 1 OVERLOAD

OL1

W

MSG, WRN, ALM

 

 

 

 

COMP 2 OVERLOAD

OL2

W

MSG, WRN, ALM

 

 

 

 

COMP 1 HIGH PRESSURE

HP1

W

MSG, WRN, ALM

 

 

 

 

COMP 2 HIGH PRESSURE

HP2

W

MSG, WRN, ALM

 

 

 

 

COMP 1 LOW PRESSURE

LP1

W

MSG, WRN, ALM

 

 

 

 

COMP 2 LOW PRESSURE

LP2

W

MSG, WRN, ALM

 

 

 

 

COMP 1 PUMPDOWN FAIL

PD1

W

MSG, WRN, ALM

 

 

 

 

COMP 2 PUMPDOWN FAIL

PD2

W

MSG, WRN, ALM

 

 

 

 

DIG SCROLL1 HIGH TEMP

HT1

W

MSG, WRN, ALM

 

 

 

 

DIG SCROLL2 HIGH TEMP

HT2

W

MSG, WRN, ALM

 

 

 

 

EL HEAT HIGH TEMP

EHO

W

MSG, WRN, ALM

 

 

 

 

Page 5 of 7

 

 

 

 

 

 

 

PASSWORD

-

W

-

 

 

 

 

DELAY

-

-

-

 

 

 

 

WORKING HRS EXCEEDED

WHE

W

0 - 9999 sec

 

 

 

 

SMOKE DETECTED

SMO

W

0 - 9999 sec

 

 

 

 

WATER UNDER FLOOR

WUF

W

0 - 9999 sec

 

 

 

 

COND PUMP-HIGH WATER

CPH

W

0 - 9999 sec

 

 

 

 

LOSS OF FLOW

LOF

W

0 - 9999 sec

 

 

 

 

STBY GLYCOL PUMP ON

SGP

W

0 - 9999 sec

 

 

 

 

STANDBY UNIT ON

STB

W

0 - 9999 sec

 

 

 

 

HUMIDIFIER PROBLEM

HUP

W

0 - 9999 sec

 

 

 

 

NO CONNECTION w/Unit1

NOC

W

internal

 

 

 

 

UNIT X DISCONNECTED

-

W

internal

 

 

 

 

LOSS OF POWER

LOP

W

internal

 

 

 

 

ENABLE - DISAB

-

-

-

 

 

 

 

WORKING HRS EXCEEDED

WHE

W

Disabled, Enabled

 

 

 

 

SMOKE DETECTED

SMO

W

Disabled, Enabled

 

 

 

 

WATER UNDER FLOOR

WUF

W

Disabled, Enabled

 

 

 

 

66

Page 72
Image 72
Emerson iCOM user manual Enable Disab Comp 1 Overload