Emerson iCOM user manual Unit Diary-Large Display Only, Unit diary parameters

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 63
Image 63

Service Menu Parameters

°C / °F

%RH SET

Table 23 Setpoints parameters

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

VSD Setpoint

VSD SET

W

0-100%

 

 

 

 

Page 4 of 5

 

 

 

Password

PASSWORD

W

-

 

 

 

 

VSD Fanspeed

FANSPEED

W

Auto, Manual, Economy

 

 

 

 

VSD Setpoint STD

VSD SET

W

HPM: 30-100%

non HPM: 60-100%

 

 

 

VSD Setpoint MIN

VSD MIN

W

HPM: 30-100%

non HPM: 60-100%

 

 

 

VSD Setpoint Dehum

VSD DEH

W

HPM: 30-100%

non HPM: 60-100%

 

 

 

VSD Setpoint No Power

VSD NOP

W

HPM: 30-100%

non HPM: 60-100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 5 of 5

 

 

 

Password

PASSWORD

W

-

 

 

 

 

SCR Control Type

CTRLTYPE

W

Tight, Standard, Economy

 

 

 

 

Start Compressor 1 At

CO1 ON

W

-150 to +100%

 

 

 

 

Stop Compressor 1 At

CO1 OFF

W

-200 to +50%

 

 

 

 

Compressor 1 Stop Delay

CO1 TD

W

0-30 min

 

 

 

 

Start Compressor 2 At

CO2 ON

W

-150 to +100%

 

 

 

 

Stop Compressor 2 At

CO2 OFF

W

-200 to +50%

 

 

 

 

Compressor 2 Stop Delay

CO2 TD

W

0-30 min

 

 

 

 

Cycle Time

CYCLET

R

0.2 – 200.0 sec

 

 

 

 

SCR Factor

SCRFACT

W

1.0 to 10.0

 

 

 

 

Actual SCR Request

ACT SCR

R

0-100%

 

 

 

 

Unit Diary—Large Display Only

Shows all entered program changes and maintenance performed on the unit.

Table 24 Unit diary parameters