Service Menu Parameters

SET

ALARMS

+ / -

Table 28 Set alarms parameters (continued)

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

TYPE

-

-

-

 

 

 

 

COMP 1 SHORT CYCLE

SC1

W

MSG, WRN, ALM

 

 

 

 

COMP 2 SHORT CYCLE

SC2

W

MSG, WRN, ALM

 

 

 

 

NO POWER

NOP

W

MSG, WRN, ALM

 

 

 

 

CONDENSER 1 FAILURE

CN1

W

MSG, WRN, ALM

 

 

 

 

CONDENSER 2 FAILURE

CN2

W

MSG, WRN, ALM

 

 

 

 

-

-

-

-

 

 

 

 

-

-

-

-

 

 

 

 

-

-

-

-

 

 

 

 

-

-

-

-

 

 

 

 

-

-

-

-

 

 

 

 

-

-

-

-

 

 

 

 

Table 29 Sensor calibration / setup parameters

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

 

 

 

 

Page 1 of 3

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Return Temperature

RTN TEMP

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Return Temperature

CAL TEMP

R

32-122°F (0-50°C)

 

 

 

 

Return Humidity

RTN HUM

W

±9.9%

 

 

 

 

Calibrated Return Humidity

CAL HUM

R

20-80%

 

 

 

 

Digiscroll 1 NTC

DS1 NTC

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Digiscroll 1 NTC

CAL DS1

R

84-313°F (29-156°C)

 

 

 

 

Digiscroll 2 NTC

DS2 NTC

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Digiscroll 2 NTC

CAL DS2

R

84-313°F (29-156°C)

 

 

 

 

 

 

 

 

 

 

 

 

Page 2 of 3

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Temperature Sensor A

TEMP A

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Temperature Sensor A

CAL A

R

32-122°F (0-50°C)

 

 

 

 

Humidity Sensor A

HUM A

W

±9.9%

 

 

 

 

Calibrated Humidity Sensor A

CAL A

R

20-80%

 

 

 

 

Temperature Sensor B

TEMP B

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Temperature Sensor B

CAL B

R

32-122°F (0-50°C)

 

 

 

 

Humidity Sensor B

HUM B

W

±9.9%

 

 

 

 

Calibrated Humidity Sensor B

CAL B

R

20-80%

 

 

 

 

 

 

 

 

 

 

 

 

Page 3 of 3

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

69

Page 75
Image 75