Emerson user manual Liebert vNSA, Ports available for connecting Liebert iCOM control devices

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 53
Image 53

Installing a Liebert iCOM Unit-to-Unit Network

Figure 29 Liebert iCOM input-output control board

P65

 

P64

P61

P63

(RJ-45 Jack)

P67

P66

Liebert vNSA

The Liebert vNSA is designed to connect multiple Liebert iCOM control devices. The Liebert vNSA contains either one or two powered industrial rail switches. An optional remote large display can be attached to the front door as well. All models have a power supply that requires connection to a single phase 120V or 240VAC power source. The enclosure features a key lock for security.

The Liebert vNSA supports autonegotiation, autopolarity and autocrossing, allowing for the use of standard network cables for connection to each port, rather than special crossover cables. The switch detects and makes adjustments for the network's speed and transmission mode, polarity and trans- mit-and-receive pins. See the Liebert vNSA user manual, SL-18840, for more details.

The number of ports available for connecting Liebert iCOM control devices varies by model as shown in Table 11. Models with a remote large display attached to the front door utilize one of the available Ethernet ports in the Liebert vNSA. Models with two switches utilize two ports to connect the switches.

Table 11 Ports available for connecting Liebert iCOM control devices

 

Liebert

 

 

 

 

 

vNSA With

 

Number of Ports

Number of Ports

Number of Ports

 

Remote

 

Used to Connect

Used to

Available to

 

Large

Total Number

Remote Large

Interconnect

Connect Liebert iCOM

Model

Display

of Ports

Display

Switches

Control Devices

Liebert vNSA8-Liebert

 

8

1

-

7

iCOM

Yes

 

 

 

 

Liebert vNSA16-

16

1

2

13

 

Liebert iCOM

 

 

 

 

 

 

 

 

 

 

 

Liebert vNSA8

No

8

-

-

8

 

 

 

 

 

Liebert vNSA16

16

-

2

14

 

 

 

 

 

 

 

47

Page 53
Image 53
Emerson user manual Liebert vNSA, Ports available for connecting Liebert iCOM control devices