Operation

The Value setting is the factory default setting on free-cooling and dual cooling units. If the tempera- ture difference between the second source cooling fluid parameter, Free-cooling Fluid Temperature (User Menu, Sensor Data) and room air is equal to or greater than the adjustable DT Between Room Air / FC Fluid (Service Menu, Setpoints) value, then the second source cooling fluid will be used to provide at least partial cooling (delta T between room and glycol = true).

Sensors used for this delta T are: room/local sensor or the return air sensor; and the glycol sensor. If this delta T is true, the following actions will be performed:

1.The Free-Cooling Status indication will show “On” instead of “Off”.

2.The compressor band will be shifted to the right by 100%, and within the first 100% the free- cooling valve band will take place (see Figure 18).

Figure 18 Second cooling source and compressorized cooling

Temp Setpoint: 70°F

Proportional Band: 8°F

Deadband: 2°F

Valve

Valve 100%

Cool 1

Cool 2

Closed

Open

On

On

 

+ 100%

 

 

½ Dead-

Cooling

 

 

 

 

 

band

2ndComp Source

70

71

72

73

74

75

76

77

78

79

0% Cooling

½ Proportional Band

½ Proportional Band

+ 200%

Band1: 2nd Source

Band 2: Compressors

Cooling

Increasing Temperature

Minimum Chilled Water Temperature—This feature permits the user to select the minimum chilled water temperature that allows simultaneous operation of the second cooling source (chilled water control) and compressor control. This feature is enabled in the Service menu under Setpoints, parameter Minimum CW Temp.

Below this minimum chilled water setpoint, parameter Minimum CW Temp Value, (Service Menu, Setpoints), the control will operate ONLY the second cooling source control, i.e., the compressor is locked out. Above the minimum chilled water setpoint, assuming the fluid temperature is below the return room air temperature (delta T between room and glycol = true), the control will operate the second cooling source control and compressor control simultaneously if needed.

If the Minimum CW Temp is disabled, the second cooling source temperature is ignored, the control will always operate the second cooling source and compressors simultaneously when the load requires it.