Operation

3.7.5User Inputs / Customer Inputs

The user can connect and specify up to four inputs depending on unit configuration. The user inputs/customer inputs are digital inputs that influence the operating mode of the unit depending on the selection. The customer input configuration settings are in the Service menu under Set Alarms, Screen 2 of 7. The choices for the customer inputs are shown in Table 7 along with their associated reaction. A terminal strip is provided in the cooling unit to connect your contact closure to. You have the ability to set the control to react on an open or closed contact.

NOTE

To enabled/disabled, delay activation and set event type (alarm, warn, message) see Event Types on page 34.

Table 7

Customer inputs

Setting

 

Reaction

 

 

 

Smoke

 

Event Only

 

 

Water Alarm

Event Only

 

 

C PMP Alarm

Event Only

 

 

 

Flow Alarm

 

Event Only

 

 

Stdby G Pmp

Event Only

 

 

 

Stdby Unit

 

Event Only

 

 

 

C-Input 1

 

Event Only

 

 

 

C-Input 2

 

Event Only

 

 

 

C-Input 3

 

Event Only

 

 

 

C-Input 4

 

Event Only

 

 

 

Rht Lockout

 

Event + Electrical Heaters Disabled

 

 

Hum Lockout

Event + Humidifier Disabled

 

 

Rht+Hum Lock

Event + Electrical Heaters and Humidifier Disabled

 

 

Comp Lockout

Event + Compressor(s) Disabled w/o Pump Down

 

 

 

Call Service

 

Event Only

 

 

 

High Temp

 

Event Only

 

 

 

Air Loss

 

Event Only

 

 

 

FC Lockout

 

Event + Free Cooling Disabled

 

 

Heater Alarm

Event + Heaters Off (PeX Only)

 

 

 

Flow AL SD

 

Event + Shut Down the Unit

 

 

 

Flow AL LC

 

Event + Lockout Compressors, No Pump Down (enabled only if at

 

 

least one compressor is on; auto-reset depends on input status)

Comp Lock PD

Event + Compressor(s) Disabled w/ Pump Down

 

 

 

Enable FC

 

Forces Free Cooling to On

 

 

 

HTRJ VFD

 

Activates the HEAT REJ VFD ALARM; no other function

 

 

HTRJ TVSS

Activates the HEAT REJ TVSS ALARM; no other function

 

 

 