Emerson iCOM Spare Part List-Large Display Only, Setpoints parameters, Event log parameters

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 57
Image 57

User Menu Parameters

7.0USER MENU PARAMETERS

°C / °F

%RH SET

User menus report general cooling unit operations and status. The password for the user menu is 1490.

The iCOM control firmware is being updated constantly. As a result, the User menu parameter tables in this manual may be slightly different than what is shown on your cooling unit's display. Please check www.liebert.com for the latest iCOM User manual updates.

Table 12 Setpoints parameters

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

Page 1 of 1

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Temperature Setpoint

TEMP SET

W

41-104°F (5-40°C)

 

 

 

 

 

 

 

20-80%

Humidity Setpoint

HUM SET

W

(settings lower than 19%

 

 

 

will be forced to 20)

Humidity Control Type

HUM CTRL

W

Relative, Compensated,

Predictive

 

 

 

Supply Limit

SUP LIM

W

Enabled, Disabled

 

 

 

 

Supply Limit Temp Value

SUP TEMP

W

41-77°F (5-25°C)

 

 

 

 

Backup Temperature

BACK TPS

W

41-104°F (5-40°C)

Setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVENT

LOG

Spare Part List—Large Display Only

Displays the various Liebert part numbers for all parts in the cooling unit to simplify ordering replacement parts.

Table 13 Spare part list parameters—large display only

 

Function

Read/

Range

 

 

 

Large Display

 

Small Display

Write

Imperial (metric)

 

 

 

 

 

Page 1 of 1

 

 

 

 

 

 

 

 

 

List of parts

 

N/A

R

-

 

 

 

 

 

Table 14 Event log parameters

 

Function

Read/

Range

 

 

 

Large Display

 

Small Display

Write

Imperial (metric)

 

 

 

 

 

Page 1 of 1

 

 

 

 

 

 

 

 

 

Last 400 events

 

Last 400 events

R

-

 

 

 

 

 

Table 15 View network parameters—large display only*

 

Function

Read/

Range

Large Display

 

Small Display

Write

Imperial (metric)

Page 1 of 1

 

 

 

 

 

 

 

 

AlarmOff, Manual, LocalOff, SystemOff,

Status Unit 1—32

 

N/A

R

AlarmStandby, Standby, TimerOff,

 

 

 

 

SystemOn, WarningOn, AlarmOn, Timer

* Permits viewing all units connected in a network. Viewable on a large display only.

51

Page 57
Image 57
Emerson iCOM Spare Part List-Large Display Only, Setpoints parameters, Spare part list parameters-large display only