Emerson iCOM user manual Dehumidification Low Limit, Dehumidification Compressor Quantity

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 35
Image 35

Operation

3.6.2Dehumidification

The Dehumidification Enable parameter (Service Menu, Options Setup) allows for enabling/disabling the dehumidification function.

A call for dehumidification is calculated in the same way as a cooling request. The components (valves, compressors) will follow this dehumidification request as soon as it is higher than the request for cooling.

Dehumidification Low Limit

Low Limit 1 and Low Limit 2 are used to avoid overcooling a room during dehumidification. When a low limit is reached, a compressor or the liquid cooling source that is used for dehumidification is dis- abled. It is re-enabled when the return air temperature rises. The Low Limit 1 and 2 settings are in the Service menu under Setpoints.

Low Limit 1: Low Limit 1 will disable one of two compressors for dehumidification. If only one com- pressor is set for dehumidification, or if the dehumidification source is chilled water, this limit will not be visible and will be inactive.

Low Limit 2: Low Limit 2 will disable both compressors for dehumidification. This limit will also stop dehumidification in single compressor units and in chilled water units.

The limits become active when the return air temperature drops below a temperature value equal to the sum of the temperature setpoint plus the value set on Low Limit 1 and 2 (the Low Limit settings are negative values).

A dehumidification source is deactivated if the return air temperature drops below the Deactivation Temperature, as in this example:

Temperature Setpoint:

70°F

Low Limit Value:

-7°F

Deactivation Temperature:

62°F

NOTE

If a cooling unit is equipped with SCR reheat and the SCR Control Type parameter is set to Tight mode, then Low Limit 2 will be ignored, see 3.5 - Temperature Control—Reheat.

Dehumidification Compressor Quantity

Under Factory Settings in the Advanced menu there is an item called Dehumidification With Comp. This item will be set to either 1, 2, 1 or 2, or BOTH. This setting determines which compressors are used for dehumidification. It also determines if Low Limit 1 will be available and impacts how the reheats will operate during dehumidification. The Dehumidification With Comp field is set when the cooling unit is built and should not be adjusted without consulting the factory first. Table 6 outlines which Low Limit settings will be available, based on the Dehumidification With Comp selection.

Table 6

Dehumidification With Comp settings

 

Available to Set Value

Dehumidification With Comp Setting

Default Setting On

 

 

 

 

 

 

[blank] (units without compressors)

All Chilled Water Units

 

 

 

 

 

 

1 (Compressor 1 dehumidifies only)

Liebert Challenger 3000, Liebert DS,

Low Limit 2 only

 

Liebert Deluxe System/3

 

 

2 (Compressor 2 dehumidifies only)

 

 

 

 

 

 

1 or 2 (Compressor 1 and 2 alternate)

 

 

 

Low Limit 1 & 2

Both (both compressors dehumidify)

 

 

 

 

Low Limit 1 & 2 will be available only on cooling units with two compressors when Dehumidification With Comp is set to BOTH (see WARNING on page 30).

29

Page 35
Image 35
Emerson iCOM Dehumidification Low Limit, Dehumidification Compressor Quantity, Dehumidification With Comp settings