4.0TEAMWORK

Unit-2-Unit (U2U) Communications via a private network will allow the following functions to be placed into operation when the requirement exists. The user must install the correct hardware (see 5.0 - Installing a Liebert iCOM Unit-to-Unit Network) and properly program the units for the selected functionality.

The Liebert iCOM network can perform the following functions:

The Teamwork Mode functions allow for multiple stages of cooling/heating and humidifica- tion/dehumidification. Teamwork Mode can be used to prevent environmental units from “fighting,” where one environmental unit might be cooling while another unit is heating.

The Standby (Lead/Lag) function allows one or more units to be set as “Running” and “Standby” for activation in case of an alarm. This function also allows the units to be programmed in a rotation to help ensure “Standby” unit operation.

The Cascade Operation function allows additional units to be staged-on based on the temperature or humidity requirement.

4.1Teamwork Modes

Groups of cooling units connected to a network can be set up to work together in any of three team- work modes: No Teamwork, Teamwork Mode 1 and Teamwork Mode 2. All Liebert iCOM-controlled cooling units on a network must be set to run in the same Teamwork mode.

4.1.1Application of Teamwork Modes

No Teamwork: Multiple zones in one room.

Teamwork Mode 1: Balanced load (small groups of units inside the same environment)

Teamwork Mode 2: Unbalanced load (large rooms, not all units will have the same load) (work well for most applications)

All units in a network will run in the same Teamwork Mode.

4.1.2No Teamwork

All cooling units work independently, responding to their own sensors.

Standby function and unit rotation are possible, but cascading is not (see Standby and Cascade on page 41). Autoset will not adjust the proportional band in Teamwork mode No.

4.1.3Teamwork Mode 1

Teamwork Mode 1 works best in small rooms with balanced heat loads. This mode does not operate based on the most demanding unit on the network. The return temperature and humidity sensor readings of all units in operation (fan on) are averaged by the master unit, Unit #1, and used for con- trol. The master unit will send the performance requests unitwise according to unit numbers, rotated by one unit every 24 hours.

In this teamwork mode most of the parameters are shared; if set in any one of the units, all other units will follow with the same settings. AutoSet will adjust the proportional band in Teamwork Mode 1, see 3.3.1 - Temperature Proportional Band.

The master unit evenly divides the system proportional band among the number of available units. Each unit will receive instruction on how to operate from the master unit based on how far the system deviates from the setpoints.

39

Page 45
Image 45
Emerson iCOM user manual Application of Teamwork Modes, No Teamwork