Service Menu Parameters

8.0SERVICE MENU PARAMETERS

°C / °F

%RH SET

Service menus allow customized settings for site operations. The password for service menu parame- ters is 5010.

The iCOM control firmware is being updated constantly. As a result, the Service menu parameter tables shown in this manual may be slightly different than what is shown on your cooling unit's dis- play. Please check www.liebert.com for the latest iCOM User manual updates.

Table 23 Setpoints parameters

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

Page 1 of 5

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Temperature Setpoint

TEMP SET

W

41-104°F (5-40°C)

 

 

 

 

Control Type

CTRL TYP

W

Proportional, PI, PID, Intelligent

 

 

 

 

Temperature Proportional Band

TEMP PB

W

2-54°F (1-30°C) autoset

 

 

 

 

Temperature Integration Time

TEMP INT

W

0-15 min, autoset

 

 

 

 

Temperature Derivative Time

TEMP DER

W

0-900 sec

 

 

 

 

AutoSet Enable

AUTOSET

W

No, Yes

 

 

 

 

Temperature DeadBand

TEMP DB

W

0-36°F (0-20°C)

 

 

 

 

Second Setpoint

2ND SETP

W

41-104°F (5-40°C)

 

 

 

 

Backup Temperature Setpoint

BACK TSP

W

41-104°F (5-40°C)

 

 

 

 

 

 

 

 

Page 2 of 5

 

 

 

 

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Humidity Setpoint

HUM SET

W

20-80%

 

 

 

 

Humidity Control Type

HUM CTRL

W

Relative, Compensated, Predictive

 

 

 

 

Humidity Proportional Band

HUM PB

W

1-20%

 

 

 

 

Humidity Integration Time

HUM INT

W

0-15 min

 

 

 

 

Humidity Deadband

HUM DB

W

0-50%

 

 

 

 

Dehum/Heat Low Limit 1

LO LIM 1

W

-9.9°F to -2.0°F

 

 

 

 

Dehum/Heat Low Limit 2

LO LIM 2

W

-9.9°F to -2.0°F

 

 

 

 

internal variable Low Limit 1 reset

 

 

-10.0°F / -2.0°F

 

 

-5.5K / -1.1K

 

 

 

internal variable Low Limit 1 reset

 

 

-10.0°F / -2.0°F

 

 

-5.5K / -1.1K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 3 of 5

 

 

 

Password

PASSWORD

W

-

 

 

 

 

Supply Limit

SUP LIM

W

Enabled, Disabled

 

 

 

 

Supply Limit Temp Value

SUP TEMP

W

41-77°F (5-25°C)

 

 

 

 

DT between Room / FC Type

FC TYPE

W

No, Contact, Value

 

 

 

 

DT between Room Air/ FC Fluid

FC DT

W

0-36°F (-18 - 2 °C)

 

 

 

 

Minimum CW Temp

MIN CW

W

No, Yes

 

 

 

 

Minimum CW Temp Value

MIN CW

W

32-68°F (0-20°C)

 

 

 

 

 

 

 

 

VSD Fanspeed

FANSPEED

W

Auto / Manual

 

 

 

 

56

Page 62