Emerson iCOM user manual System / network setup parameters-large display only

Models: iCOM

1 84
Download 84 pages 5.7 Kb
Page 76
Image 76

Service Menu Parameters

+ / -

NETWORK

Table 29 Sensor calibration / setup parameters

Function

 

Read/

Range

 

 

Large Display

Small Display

Write

Imperial (metric)

Freecool Sensor PTC or NTC

FC SNSR

W

PTC, NTC

 

 

 

 

Freecool Sensor

FC SNSR

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Freecool Sensor

CAL FC

R

4-113°F (-15 to 45°C)

 

 

 

 

Supply Sensor PTC or NTC

SUP SNSR

W

PTC, NTC

 

 

 

 

Supply Sensor

SUP TEMP

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Supply Sensor

CAL SUP

R

32-122°F (0-50°C)

 

 

 

 

Temperature Sensor C

TEMP C

W

±18°F (±9.9°C)

 

 

 

 

Calibrated Temperature Sensor C

CAL C

R

32-122°F (0-50°C)

 

 

 

 

Humidity Sensor C

HUM C

W

±9.9%

 

 

 

 

Calibrated Humidity Sensor C

CAL C

R

20-80%

 

 

 

 

Table 30 System / network setup parameters—large display only

Function

 

Read/

Range

 

 

 

Large Display

 

Small Display

Write

Imperial (metric)

 

 

 

 

 

Page 1 of 2

 

 

 

 

 

 

 

Password

 

PASSWORD

W

-

 

 

 

 

 

Number of Connected

 

W

1-32

Units

 

 

 

 

 

 

Teamwork Mode

 

W

No, 1, 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuration Safe

 

R

Not Available, Invalid, OK,

 

 

Changed, Updating

 

 

 

 

Configuration Safe

 

W

No, SaveLoad

 

 

 

 

 

Network Safe

 

R

Not Available, Invalid, OK,

 

 

Changed, Updating

 

 

 

 

Network Safe

 

W

No, Save, Load

 

 

 

 

 

SW Version

 

W

 

 

 

 

 

 

Page 2 of 2

 

 

 

 

 

 

 

Password

 

PASSWORD

W

-

 

 

 

 

 

IP Address

 

W

IP Range

 

 

 

 

 

70

Page 76
Image 76
Emerson iCOM user manual System / network setup parameters-large display only